713.11 Sterilizer Vent Stack Sizes
Go To Full Code Chapter
713.11.1 Bedpan Steamers
The minimum size of a sterilizer vent serving a bedpan steamer shall be 11/2 inches (38 mm) in diameter. Multiple installations shall be sized in accordance with Table 713.11.1.
STACK SIZE (inches) |
CONNECTION SIZE | ||
11/2" | 2" | ||
11/2a | 1 | or | 0 |
2a | 2 | or | 1 |
2b | 1 | and | 1 |
3a | 4 | or | 2 |
3b | 2 | and | 2 |
4a | 8 | or | 4 |
4b | 4 | and | 4 |
For SI: 1 inch = 25.4 mm.
- Total of each size.
- Combination of sizes.
713.11.2 Boiling-Type Sterilizers
The size of a sterilizer vent stack shall be not less than 2 inches (51 mm) in diameter where serving a utensil sterilizer and not less than 11/2 inches (38 mm) in diameter where serving an instrument sterilizer. Combinations of boiling-type sterilizer vent connections shall be sized in accordance with Table 713.11.1.
713.11.3 Pressure Sterilizers
Pressure sterilizer vent stacks shall be 21/2 inches (64 mm) minimum. Those serving combinations of pressure sterilizer exhaust connections shall be sized in accordance with Table 713.11.3.
STACK SIZE (inches) |
CONNECTION SIZE | |||
3/4" | 1" | 11/4" | 11/2" | |
11/2a | 3 or | 2 or | 1 | — |
11/2b | 2 and | 1 | — | — |
2a | 6 or | 3 or | 2 or | 1 |
2b | 3 and | 2 | — | — |
2b | 2 and | 1 and | 1 | — |
2b | 1 and | 1 and | — | 1 |
3a | 15 or | 7 or | 5 or | 3 |
3b | 1 and | 1 and 5 and |
2 and | 2 1 |
For SI: 1 inch = 25.4 mm.
- Total of each size.
- Combination of sizes.
713.11.4 Pressure Instrument Washer Sterilizer Sizes
The diameter of a sterilizer vent stack serving an instrument washer sterilizer shall be not less than 2 inches (51 mm). Not more than two sterilizers shall be installed on a 2-inch (51 mm) stack, and not more than four sterilizers shall be installed on a 3-inch (76 mm) stack.
Upcodes Diagrams
Related Code Sections
713.11 Sanitary Drainage, Sterilizer Vent Stack Sizes
Sterilizer vent stack sizes shall comply with Sections 713.11.1 through 713.11.4 ...
713.11 Sanitary Drainage, Sterilizer Vent Stack Sizes
Sterilizer vent stack sizes shall comply with Sections 713.11.1 through 713.11.4 ...
713.11.4 Sanitary Drainage, Pressure Instrument Washer Sterilizer Sizes
The diameter of a sterilizer vent stack serving an instrument washer sterilizer shall be not less than 2 inches (51 mm). Not more than two ...
713.11.1 Sanitary Drainage, Bedpan Steamers
Sizes Permitted to Various-sized Sterilizer Vent Stacks)
STACK SIZE (inches)
CONNECTION SIZE
11/2"
2"
11/2a
1
or
0 ...
713.11.1 Sanitary Drainage, Bedpan Steamers
Permitted to Various-sized Sterilizer Vent Stacks)
STACK SIZE (inches)
CONNECTION SIZE
11/2"
2"
11/2a
1
or
0 ...