Where stepped foundations occur, the following requirements apply:
  1. Where the height of a required braced wall panel that extends from foundation to floor above varies more than 4 feet (1220 mm), the braced wall panel shall be constructed in accordance with Figure R602.11.3.
  2. Where the lowest floor framing rests directly on a sill bolted to a foundation not less than 8 feet (2440 mm) in length along a line of bracing, the line shall be considered as braced. The double plate of the cripple stud wall beyond the segment of footing that extends to the lowest framed floor shall be spliced by extending the upper top plate a minimum of 4 feet (1219 mm) along the foundation. Anchor bolts shall be located a maximum of 1 foot and 3 feet (305 and 914 mm) from the step in the foundation.
  3. Where only the bottom of the foundation is stepped and the lowest floor framing rests directly on a sill bolted to the foundations, the requirements of Section R602.11.1 shall apply.



     


    For SI: 1 inch 25.4 mm, 1 foot = 304.8 mm.

    Note: Where footing Section "A" is less than 8 feet long in a 25-foot-long wall, install bracing at cripple stud wall.

    FIGURE R602.11.3
    STEPPED FOUNDATION CONSTRUCTION

Related Code Sections

R602.11.3 Wall Construction, Stepped Foundations
Where stepped foundations occur, the following requirements apply: Where the height of a required braced wall panel that extends from foundation ...
13.3.1.3 Foundations,
In sloped, stepped, or tapered foundations, depth and location of steps or angle of slope shall be such that design requirements are satisfied ...