Steel joist placement plans shall be provided to show the steel joist products as specified on the approved construction documents and are to be utilized for field installation in accordance with specific project requirements as stated in Section 2207.2. Steel joist placement plans shall include, at a minimum, the following:
  1. Listing of applicable loads as stated in Section 2207.2 and used in the design of the steel joists and joist girders as specified in the approved construction documents.
  2. Profiles for joist and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.
  3. Connection requirements for:
    3.1.  Joist supports.
    3.2.  Joist girder supports.
    3.3.  Field splices.
    3.4.  Bridging attachments.
  4. Live and total load deflection criteria for joists and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.
  5. Size, location and connections for bridging.
  6. Joist headers.
Steel joist placement plans do not require the seal and signature of the joist manufacturer's registered design professional.

Related Code Sections

2207.4 Steel, Steel Joist Drawings
Steel joist placement plans shall be provided to show the steel joist products as specified on the approved construction documents ...
2207.4 Steel, Steel Joist Drawings
Steel joist placement plans shall be provided to show the steel joist products as specified on the approved construction documents ...
Chapter 22 Steel
composite construction), cold-formed steel, steel joists, steel cable structures and steel storage racks. This chapter specifies appropriate design ...
2211.1.3.1 Steel, Truss Design Drawings
The truss design drawings shall conform to the requirements of Section I1 of AISI S202 and shall be provided with the shipment of trusses delivered ...