1216.1 Steam Traps
For other than one-pipe steam systems, each heat-distribution unit shall be supplied with a steam trap that is listed for the application.
1216.2 Sloping for Two-Pipe System
Two-pipe steam system piping and heat-distribution units shall be sloped down at not less than 1/8 inch per foot (10.4 mm/m) in the direction of the steam flow.
1216.3 Sloping for One-Pipe System
One-pipe steam system piping and heat-distribution units shall be sloped down at not less than 1/8 inch per foot (10.4 mm/m) towards the steam boiler, without trapping.
1216.4 Automatic Air Vents
Steam automatic air vents shall be installed to eliminate air pressure in heat-distribution units on gravity steam piping systems. Air vents shall not be used on a vacuum system.
1216.5 Condensate Flow
System piping shall be installed to allow condensate to flow to the condensate receiver or steam boiler either by gravity or pump-assisted.
1216.6 Steam-Distribution Piping
Where multi-row elements are installed in an enclosure, they shall be top fed and piped in parallel down to the steam trap. A single steam trap for each row of heating elements shall be installed. Where the size of the return header is increased by a minimum of one pipe size, a single steam trap shall be permitted to be installed for multiple rows. Where multiple steam unit heaters are installed, an individual steam trap for each unit shall be installed.

Related Code Sections

1216.0 Hydronics, Steam Systems
For other than one-pipe steam systems, each heat-distribution unit shall be supplied with a steam trap that is listed for the application ...
1216.5 Hydronics, Condensate Flow
System piping shall be installed to allow condensate to flow to the condensate receiver or steam boiler either by gravity or pump-assisted ...
L 408.1.1 Sustainable Practices, Condensate Drainage Recovery
Condensate from air-conditioning, boiler and steam systems used to supply water for non-potable water systems shall be in accordance with Section ...