319.0 Steam and Hot-Water Systems
JUMP TO FULL CODE CHAPTER
[OSHPD 1, 1R, 4 & 5]
Boiler feed pumps, condensate return pumps,
fuel oil pumps, and heating circulating pumps shall be
connected and installed to provide standby service in the
event of pump failure. Installation of duplex pumps or
provision of a spare pump will meet this requirement.
At least two sources of heat (e.g. two pieces of
equipment) shall be provided for supplying essential
services such as sterilizers, hot water for dishwashing,
and domestic hot water for minimum patient service,
such as handwashing and baths. Booster heaters for
dishwashing providing 125°F to 180°F (52°C to 82°C)
water may be counted as the second source of heat for
that service.
[OSHPD 2 & 4]
Boilers, if provided, shall accommodate Section 319.1.
Two or more interconnected water heaters are
an acceptable means to provide two sources of heat for
hot water (See Section 319.1.5).
Related Code Sections
319.0 General Regulations, Steam and Hot-Water Systems
least two sources of heat (e.g. two pieces of
equipment) shall be provided for supplying essential
services such as sterilizers, hot water for dishwashing ...
319.0 General Regulations, Steam and Hot-Water Systems
, hot water for dishwashing,
and domestic hot water for minimum patient service,
such as handwashing and baths. Booster heaters for
dishwashing ...
319.0 General Regulations, Steam and Hot-Water Systems
least two sources of heat (e.g. two pieces of
equipment) shall be provided for supplying essential
services such as sterilizers, hot water for dishwashing ...
319.1 General Regulations, Requirements for Hospitals and Optional Services Provided in Correctional Treatment Centers
least two sources of heat (e.g. two pieces of
equipment) shall be provided for supplying essential
services such as sterilizers, hot water for dishwashing ...
California Mechanical Code 2019 > 3 General Regulations > 319.0 Steam and Hot-Water Systems > 319.1 Requirements for Hospitals and Optional Services Provided in Correctional Treatment Centers
319.1.5 General Regulations,
At least two sources of heat (e.g. two pieces of
equipment) shall be provided for supplying essential
services such as sterilizers, hot water ...
California Mechanical Code 2019 > 3 General Regulations > 319.0 Steam and Hot-Water Systems > 319.1 Requirements for Hospitals and Optional Services Provided in Correctional Treatment Centers > 319.1.5