systems. Stationary storage battery systems, as regulated by Section 608 of the Fire Code of New York State, shall be provided with ventilation in accordance with this chapter and Section 502.4.1 or 502.4.2. [F]

Exception: Lithium-ion batteries shall not require ventilation.
502.4.1 Hydrogen Limit in Rooms
For flooded lead acid, flooded nickel cadmium and VRLA batteries, the ventilation system shall be designed to limit the maximum concentration of hydrogen to 1.0 percent of the total volume of the room. [F]
502.4.2 Ventilation Rate in Rooms
Continuous ventilation shall be provided at a rate of not less than 1 cubic foot per minute per square foot (cfm/ft 2 ) [0.00508 m 3 /(s • m 2 )] of floor area of the room. [F]

Related Code Sections

502.4 Exhaust Systems, Stationary Storage Battery
systems. Stationary storage battery systems, as regulated by Section 608 of the Fire Code of New York State, shall be provided with ventilation ...
502.4 Exhaust Systems, Stationary Storage Battery Systems
Stationary storage battery systems, as regulated by Section 608 of the International Fire Code, shall be provided with ventilation in accordance ...
Section 608 Building Services and Systems, Stationary Storage Battery Systems
Stationary storage battery systems having an electrolyte capacity of more than 50 gallons (189 L) for flooded lead acid, nickel cadmium (Ni-Cd ...