1206.2.8.3 Stationary Battery Arrays
JUMP TO FULL CODE CHAPTER
Storage batteries, prepackaged stationary storage battery systems and preengineered stationary storage battery systems shall be segregated into stationary battery arrays not exceeding 50 kWh (180 megajoules) each. Each stationary battery array shall be spaced not less than 3 feet (914 mm) from other stationary battery arrays and from walls in the storage room or area. The storage arrangements shall comply with Chapter 10.
Exceptions:
- Lead-acid and nickel-cadmium storage battery arrays.
- Listed preengineered stationary storage battery systems and prepackaged stationary storage battery systems shall not exceed 250 kWh (900 megajoules) each.
- The fire code official is authorized to approve listed, preengineered and prepackaged battery arrays with larger capacities or smaller battery array spacing if large-scale fire and fault condition testing conducted or witnessed and reported by an approved testing laboratory is provided showing that a fire involving one array will not propagate to an adjacent array, and be contained within the room for a duration equal to the fire-resistance rating of the room separation specified in Table 509 of the International Building Code.
Related Code Sections
1206.2.8.3 Energy Systems, Stationary Battery Arrays
into stationary battery arrays not exceeding 50 kWh (180 megajoules) each. Each stationary battery array shall be spaced not less than 3 feet (914 mm) from ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1206 Electrical Energy Storage Systems > 1206.2 Stationary Storage Battery Systems > 1206.2.8 Location and Construction > 1206.2.8.3 Stationary Battery Arrays
Section 1202 Energy Systems, Definitions
The following terms are defined in Chapter 2:
BATTERY SYSTEM, STATIONARY STORAGE.
BATTERY TYPES.
Lead-acid battery.
CAPACITOR ARRAY ...
3115.1 Special Construction, General
as existing relocatable buildings complying with Chapter 14 of the International Existing Building Code . Stationary storage battery arrays located ...
Building Code 2021 of Colorado > 31 Special Construction > 3115 Intermodal Shipping Containers > 3115.1 General
1206.2.3.1 Energy Systems, Fault Condition
Only single-failure modes shall be considered. Thermal runaway condition in a single-battery storage rack, module or array. Failure of any ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1206 Electrical Energy Storage Systems > 1206.2 Stationary Storage Battery Systems > 1206.2.3 Hazard Mitigation Analysis > 1206.2.3.1 Fault Condition
1206.2.3 Energy Systems, Hazard Mitigation Analysis
any of the following conditions: Battery technologies not specifically identified in Table 1206.2 are provided. More than one stationary storage ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1206 Electrical Energy Storage Systems > 1206.2 Stationary Storage Battery Systems > 1206.2.3 Hazard Mitigation Analysis