F 1201.1 Static Pressure Testing
JUMP TO FULL CODE CHAPTER
Following fabrication, assembly, and installation of the piping distribution system, exterior connection panel, and interior cylinder fill panels, the Authority Having Jurisdiction shall witness the pneumatic testing of the complete system at a test pressure of not less than 7500 psi (51 711 kPa) using oil-free dry air, nitrogen, or argon. A pneumatic test of not less than 24 hours shall be performed. During this test, all fittings, joints, and system components shall be inspected for leaks. A solution compatible with the system component materials shall be used on each joint and fitting. Defects in the system or leaks detected shall be documented on an inspection report, repaired or replaced. As an alternate, a pressure-decay test in accordance with ASME B31.3 shall be permitted.
Related Code Sections
F 1201.1 Firefighter Breathing Air Replenishment Systems, Static Pressure Testing
, the Authority Having Jurisdiction shall witness the pneumatic testing of the complete system at a test pressure of not less than 7500 psi (51 711 kPa ...
Uniform Plumbing Code 2018 of Nevada > F Firefighter Breathing Air Replenishment Systems > F 1201.0 System Acceptance and Certification > F 1201.1 Static Pressure Testing
C403.2.7.1.3 [CE] Commercial Energy Efficiency, High-Pressure Duct Systems
= The measured leakage rate in cfm per 100 square feet of duct surface. P = The static pressure of the test. Documentation shall ...
Energy Conservation Code 2012 of Nevada > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.2 Provisions Applicable to All Mechanical Systems (Mandatory) > C403.2.7 Duct and Plenum Insulation and Sealing > C403.2.7.1 Duct Construction > C403.2.7.1.3 High-Pressure Duct Systems
C403.11.2.3 [CE] Commercial Energy Efficiency, High-Pressure Duct Systems (Mandatory)
= The measured leakage rate in cfm per 100 square feet of duct surface. P = The static pressure of the test. Documentation shall be furnished ...
Energy Conservation Code 2018 of Nevada > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.11 Construction of HVAC System Elements (Mandatory) > C403.11.2 Duct Construction (Mandatory) > C403.11.2.3 High-Pressure Duct Systems (Mandatory)
3.8.2.1.5 Definitions, Residual Hydrant.
The hydrant that is used for measuring static and residual pressures during a flow test. [ 24, 2013] ...
Standard for the Installation of Sprinkler Systems 2016 of Nevada > 3 Definitions > 3.8 Private Water Supply Piping Definitions > 3.8.2 Hydrant Definitions From NFPA 24 > 3.8.2.1 Hydrant. > 3.8.2.1.5 Residual Hydrant.
25.2.4 Systems Acceptance, Pressure-Reducing Valves
Each pressure-reducing valve shall be tested upon completion of installation to ensure proper operation under flow and no-flow conditions ...
Standard for the Installation of Sprinkler Systems 2016 of Nevada > 25 Systems Acceptance > 25.2 Acceptance Requirements > 25.2.4 Pressure-Reducing Valves