Standpipe and hose systems shall be provided for all airport terminal buildings in excess of two stories [35 ft (10.7 m)] in height or 100 ft (30.5 m) in shortest horizontal dimension. Standpipe and hose systems shall be installed in accordance with Section 13.2. [415:4.5.4]
21.2.10.1
Class I standpipe systems shall be provided in buildings protected throughout by an approved automatic sprinkler system. Each 21/2 in. (63.5 mm) hose connection shall be equipped with a 21/2 in. x 11/2 in. (63.5 mm x 38 mm) reducer and cap. [415:4.5.4.1]
21.2.10.2
Class III standpipe systems shall be provided in nonsprinklered buildings. Paragraphs 5.3.3.1 and 5.3.3.2 of NFPA 14 for Class III systems shall be applicable to this requirement. [415:4.5.4.2]
Upcodes Diagrams

Related Code Sections

21.2.10 Airports and Heliports, Standpipe and Hose Systems
Standpipe and hose systems shall be provided for all airport terminal buildings in excess of two stories [35 ft (10.7 m)] in height or 100 ft (30.5 m ...
21.2.10 Airports and Heliports, Standpipe and Hose Systems
Standpipe and hose systems shall be provided for all airport terminal buildings in excess of two stories [35 ft (10.7 m)] in height or 100 ft (30.5 m ...
61.2.5.2 Aerosol Products, Standpipe and Hose System
Installations of standpipe and hose systems, where required by this Code and NFPA 30B, shall be designed and installed in accordance with Section ...
61.2.6.2 Aerosol Products, Standpipe and Hose System
Installations of standpipe and hose systems, where required by this Code and NFPA 30B, shall be designed and installed in accordance with Section ...
13.2.1 Fire Protection Systems, General
The design and installation of standpipe systems shall be in accordance with Section 13.2 and NFPA 14, Standard for the Installation of Standpipe ...