1318.11 Standing Pressure Tests — For Category 3 Gas Powered Device Distribution Piping
JUMP TO FULL CODE CHAPTER
After successful completion of the initial pressure tests under Section 1318.8.7, Category 3 gas-powered device distribution piping shall be subjected to a standing pressure test, which includes the following:
- Tests shall be conducted after the installation of outlet valves and other distribution system components (e.g. pressure indicators and line pressure relief valves).
- The source valve shall be closed unless the source gas is being used for the test.
- The piping systems shall be subjected to a 24 hour standing pressure testing using oil-free, dry nitrogen NF or the system gas.
- Test pressures shall be 20 percent above the normal system operating line pressure.
- At the conclusion of the tests, there shall be no change in the test pressure greater than a gauge pressure of 5 psi (34 kPa).
- Leaks, if any, shall be located, repaired (if permitted), or replaced (if required), and retested. [NFPA 99:5.3.12.2.9]
Related Code Sections
1318.11 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Standing Pressure Tests — For Category 3 Gas Powered Device Distribution Piping
After successful completion of the initial pressure tests under Section 1318.8.7, Category 3 gas-powered device distribution piping shall ...
Uniform Plumbing Code 2018 of Nevada > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1318.0 Testing and Inspection > 1318.11 Standing Pressure Tests — For Category 3 Gas Powered Device Distribution Piping
1318.6 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Initial Pressure Test — Category 3 Copper Piping Systems
Initial pressure tests shall be conducted as follows:
After blowdown of the distribution piping.
After installation of outlet and inlet shutoff ...
Uniform Plumbing Code 2018 of Nevada > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1318.0 Testing and Inspection > 1318.6 Initial Pressure Test — Category 3 Copper Piping Systems
1313.3 Fuel Gas Piping, Test Pressure
This inspection shall include an air, CO2, or nitrogen pressure test, at which time the gas piping shall stand a pressure of not less than 10 psi (69 ...
Uniform Mechanical Code 2018 of Nevada > 13 Fuel Gas Piping > 1313.0 Pressure Testing and Inspection > 1313.3 Test Pressure
1213.3 Fuel Gas Piping, Test Pressure
This inspection shall include an air, CO2, or nitrogen pressure test, at which time the gas piping shall stand a pressure of not less than 10 psi (69 ...
Uniform Plumbing Code 2018 of Nevada > 12 Fuel Gas Piping > 1213.0 Pressure Testing, Inspection, and Purging > 1213.3 Test Pressure
1318.10 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Standing Pressure Tests — Medical Vacuum Piping Systems
After successful completion of the initial pressure tests under Section 1318.5 through Section 1318.5.3, vacuum distribution piping shall ...
Uniform Plumbing Code 2018 of Nevada > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1318.0 Testing and Inspection > 1318.10 Standing Pressure Tests — Medical Vacuum Piping Systems