Standby power shall be provided to elevators in the following categories:
  1. Elevator(s) in high-rise buildings covered by Section 403.1, other than Group R-2 occupancies, as required by Section 403.4.8.4.1;
  2. Elevator(s) in high-rise buildings in Group R-2 occupancies more than 125 feet (38 100 mm) in height, as required by Section 403.4.8.4.2;
  3. Elevator(s) in underground buildings, as required by Section 405.8;
  4. Elevator(s) in Groups B, E, and R-1 occupancies that are subject to Section 2702.2.20; and
  5. Elevator(s) serving as accessible means of egress pursuant to Section 1009.4.