In standard roll-in showers, the controls and hand shower shall not be located above the seat. Controls and hand showers shall be located according to the following:
  1. On the back wall,
  2. At a height of 38 inches (965 mm) minimum and 48 inches (1220 mm) maximum above the shower floor and
  3. 16 inches (405 mm) minimum and 27 inches (685 mm) maximum from the wall behind the seat.
FIGURE 608.4.2
STANDARD ROLL-IN-TYPE SHOWER CONTROLS AND HAND SHOWER LOCATION