Where stairways and stepped aisles are in a straight run, transitions shall have one of the following:
  1. A depth of not less than 22 inches (559 mm) where the treads on the descending side of the transition have greater depth.
  2. A depth of not less than 30 inches (762 mm) where the treads on the descending side of the transition have lesser depth.