1022.8 Stairway Identification and Floor Level Signs
JUMP TO FULL CODE CHAPTER
A floor identification sign shall be provided at each floor landing within exit enclosures connecting more than three stories. Such sign shall designate:
- The floor level;
- The terminus of the top and bottom of the exit enclosure;
- The identification of the stair or ramp;
- The story of the exit discharge; and
- The availability of roof access from the enclosure for the Fire Department.
Floor level identification signs in tactile characters complying with ICC A117.1 shall be located at each floor level landing adjacent to the door on the stair side.
Stairway and floor identification signs required by Sections 1022.8.1 and 1022.8.2 shall comply with all of the following requirements:
- The signs shall be a minimum size of 18 inches (457 mm) by 12 inches (305 mm).
- The alphabetic letters designating the identification of the stair enclosure shall be a minimum of 11/2 inches (38 mm) in height.
- The number designating the floor level shall be a minimum of 5 inches (127 mm) in height and located in the center of the sign.
- All other lettering and numbers shall be a minimum of 1 inch (25 mm) in height.
- Characters and their background shall have a nonglare finish. Characters shall contrast with their background, with either light characters on a dark background or dark characters on a light background.
- When signs required by Section 1022.8 are installed in interior exit enclosures of buildings subject to Section 1024, the signs shall be made of the same luminous materials as required by Section 1024.4.
Where doors serving vertical exit enclosures are locked on the stair side, signage shall be posted in compliance with Sections 1030.4.1, 1030.4.2 and 1030.4.3.
Related Code Sections
1023.9 Means of Egress, Stairway Identification and Floor Level Signs
Signs identifying stairways shall comply with Section 1023.9.1. Signs identifying floor levels shall comply with Sections 1023.9.2 through 1023.9.5 ...
NYC Building Code 2022 > 10 Means of Egress > 1023 Interior Exit Stairways and Ramps > 1023.9 Stairway Identification and Floor Level Signs
1022.8 Means of Egress, Stairway Identification and Floor Level Signs
Signs identifying stairways and floor levels shall comply with Sections 1022.8.1 through 1022.8.5 ...
NYC Building Code 2014 > 10 Means of Egress > 1022 Exit Enclosures > 1022.8 Stairway Identification and Floor Level Signs
1023.9.2 Means of Egress, Floor Identification Signs
sign shall designate:
The floor level;
The terminus of the top and bottom of the interior exit stairway and ramp;
The identification ...
NYC Building Code 2022 > 10 Means of Egress > 1023 Interior Exit Stairways and Ramps > 1023.9 Stairway Identification and Floor Level Signs > 1023.9.2 Floor Identification Signs
1023.9.1 Means of Egress, Stairway Identification Signs
A stairway identification sign indicating each stair by alphabetic letter shall be posted on both sides of each stair door. The alphabetic letters ...
NYC Building Code 2022 > 10 Means of Egress > 1023 Interior Exit Stairways and Ramps > 1023.9 Stairway Identification and Floor Level Signs > 1023.9.1 Stairway Identification Signs
1023.9.3 Means of Egress, Accessible Floor Level Identification Signs
Floor level identification signs in visual characters, raised characters and braille complying with ICC A117.1 shall be located at each floor level ...
NYC Building Code 2022 > 10 Means of Egress > 1023 Interior Exit Stairways and Ramps > 1023.9 Stairway Identification and Floor Level Signs > 1023.9.3 Accessible Floor Level Identification Signs