Article 9 Stair and Elevator Signs

Jump To Full Code Chapter
§27-390 Applicability
*This article is applicable to all buildings and existing buildings which have at least one elevator which is subject to periodic inspections pursuant to section 27-998, and any existing office building occupied or arranged to be occupied for an occupant load of more than one hundred persons above or below the street level or more than a total of five hundred persons in the entire building.

* NB Amended L.L. 96/85 § 3, language juxtaposed per Ch. 907/85 § 14
§27-391 Signs at Elevator Landings
A sign shall be posted and maintained on every floor at the elevator landing. The sign shall read "IN CASE OF FIRE, USE STAIRS UNLESS OTHERWISE INSTRUCTED". The lettering shall be at least one-half inch block letters in red with white background or as otherwise approved by the commissioner. Such lettering shall be properly spaced to provide good legibility. The sign shall also contain a diagram showing the location where it is posted and the location and letter identification of the stairs on the floor. The sign shall be at least ten inches by twelve inches, located directly above a call button and securely attached to the wall or partition. The top of such sign shall not be above six feet from the floor level. The diagram on such sign may be omitted provided that signs containing such diagram are posted in conspicuous places on the respective floor. In such case, the sign at the elevator landing shall be at least two and one half inches by ten inches and the diagram signs shall be at least eight inches by twelve inches.
§27-392 Floor Numbering Signs
A sign shall be posted and maintained within each stair enclosure on every floor, indicating the number of the floor. The numerals shall be of bold type and at least three inches high. The numerals and background shall be in contrasting colors. The sign shall be securely attached to the stair side of the door.
§27-393 Stair and Elevator Identification Signs
Each stair and each bank of elevators shall be identified by an alphabetic letter. A sign indicating the letter of identification for the elevator bank shall be posted and maintained at each elevator landing directly above or as part of the sign specified in section 27-391 of this article. The stair identification sign shall be posted and maintained on the occupancy side of the stair door. The letter on the sign shall be at least three inches high, of bold type and of contrasting color from the background. Such signs shall be securely attached.
§27-394 Stair Re-entry Signs in Office Buildings
Signs shall be posted and maintained on the stair door at each floor in buildings classified in occupancy group E occupied or arranged to be occupied for an occupant load of more than one hundred persons above or below the street level or more than a total of five hundred persons in the entire building indicating whether re-entry is provided into the building and the floor where such re-entry is provided. The lettering and numerals of the signs shall be at least one-half inch high of bold type. The lettering and background shall be contrasting colors and the signs shall be securely attached approximately five feet above the floor. The signs shall read as follows and may be either independent or combined with the corresponding sign required by sections 27-392 and 27-393 of this article.

(a) Where no re-entry is provided from the stairs to any floor, the sign shall read "NO RE-ENTRY FROM THIS STAIR" and such sign shall be on the occupancy side of the stair door at each floor. No re-entry sign shall be required on the stair side of the door.

(b) Where re-entry is provided to specified floors:

(1) On the stair side of the door at floors where re-entry is provided, the sign shall read "RE-ENTRY ON THIS FLOOR".

(2) Where no re-entry is provided on that floor, the sign on the stair side of the door shall read "NO RE-ENTRY, NEAREST RE-ENTRY ON THE AND FLOORS". The floor numbers of the nearest re-entry below and the nearest re-entry floor above shall be entered in the blank spaces.
§27-395 Materials for Signs
Signs required by this article shall be of metal or other durable material.
§27-396 Signs in Existing Buildings
(a) Signs installed prior to the enactment of this article may be accepted by the commissioner, provided that such signs will adequately accomplish the intended purpose.

(b) In buildings existing prior to January eighteenth, nineteen hundred seventy-three, the commissioner may modify the requirements as to location of signs where compliance would cause practical difficulty or undue hardship.

(c) All existing buildings not already subject to the requirements of this article as of January eighteenth, nineteen hundred seventy-three shall comply with the requirements of this article on or before October first, nineteen hundred eighty-five.

Related Code Sections

Article 9 Means of Egress, Stair and Elevator Signs
and maintained on every floor at the elevator landing. The sign shall read "IN CASE OF FIRE, USE STAIRS UNLESS OTHERWISE INSTRUCTED". The lettering shall ...
§27-394 Means of Egress, Stair Re-entry Signs in Office Buildings
Signs shall be posted and maintained on the stair door at each floor in buildings classified in occupancy group E occupied or arranged to be occupied ...
§27-390 Means of Egress, Applicability
*This article is applicable to all buildings and existing buildings which have at least one elevator which is subject to periodic inspections ...
3002.3.1 Elevators and Conveying Systems, Stair and Elevator Identification Signs
Each stair and each bank of elevators shall be identified by an alphabetic letter. A sign indicating the letter of identification for the elevator ...
3002.3.1 Elevators and Conveying Systems, Stair and Elevator Identification Signs
Each stair and each bank of elevators shall be identified by an alphabetic letter. A sign indicating the letter of identification for the elevator ...