1015.6 Stage Means of Egress

NYC Building Code 2014 > 10 Means of Egress > 1015 Exit and Exit Access Doorways > 1015.6 Stage Means of Egress
JUMP TO FULL CODE CHAPTER
Where a minimum of two means of egress are required pursuant to Section 410.5.3, one means of egress shall be provided on each side of the stage.

1015.6.1 Gallery, Gridiron and Catwalk Means of Egress

The means of egress from lighting and access catwalks, galleries and gridirons shall meet the requirements for occupancies in Group F-2.

Exceptions:

1. A minimum width of 22 inches (559 mm) is permitted for lighting and access catwalks.

2. Stairways required by this subsection need not be enclosed.

3. Stairways with a minimum width of 22 inches (559 mm), ladders or spiral stairs are permitted in the means of egress.

4. A second means of egress is not required from these areas where a means of escape to a floor or to a roof is provided.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1014.6 Means of Egress, Stage Means of Egress
Where two means of egress are required based on the stage size or occupant load, one means of egress shall be provided on each side of the stage ...
NYC Building Code 2008 > 10 Means of Egress > 1014 Exit and Exit Access Doorways > 1014.6 Stage Means of Egress
1015.6 Means of Egress, Stage Means of Egress
Where a minimum of two means of egress are required pursuant to Section 410.5.3, one means of egress shall be provided on each side of the stage ...
NYC Building Code 2014 > 10 Means of Egress > 1015 Exit and Exit Access Doorways > 1015.6 Stage Means of Egress
410.3.3 Special Detailed Requirements Based on Use and Occupancy, Exterior Stage Doors
that are located on the stage for means of egress or loading and unloading purposes, and that are likely to be open during occupancy of the theater, shall ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 410 Stages and Platforms > 410.3 Stages > 410.3.3 Exterior Stage Doors
410.3.3 Special Detailed Requirements Based on Use and Occupancy, Exterior Stage Doors
openings that are located on the stage for means of egress or loading and unloading purposes, and that are likely to be open during occupancy ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 410 Stages and Platforms > 410.3 Stages > 410.3.3 Exterior Stage Doors
Article 13 Special Occupancy Structures [PDF] (page 13)
to the passageways, courts or streets shall be provided on opposite sides of the stage level. (12.10.2.8). h. Required exits from stage gridirons.-Two means of exit ...
NYC 1938 Code [PDF] > 13 Special Occupancy Structures
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Contact Careers Terms Privacy
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US