917.2 Stack Size
Go To Full Code Chapter
Drainage stacks shall be sized in accordance with Table 917.2. Stacks shall be uniformly sized based on the total connected drainage fixture unit load. The stack vent shall be the same size as the drainage stack. A 3-inch (76 mm) stack shall serve not more than two water closets.
SINGLE STACK SIZE
STACK SIZE (inches) | MAXIMUM CONNECTED DRAINAGE FIXTURE UNITS | ||
Stacks less than 75 feet in height | Stacks 75 feet to less than 160 feet in height | Stacks 160 feet and greater in height | |
3 | 24 | NP | NP |
4 | 225 | 24 | NP |
5 | 480 | 225 | 24 |
6 | 1,015 | 480 | 225 |
8 | 2,320 | 1,015 | 480 |
10 | 4,500 | 2,320 | 1,015 |
12 | 8,100 | 4,500 | 2,320 |
15 | 13,600 | 8,100 | 4,500 |
NP = Not Permitted
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Upcodes Diagrams
Related Code Sections
917.2 Vents, Stack Size
Drainage stacks shall be sized in accordance with Table 917.2. Stacks shall be uniformly sized based on the total connected drainage fixture unit ...
917.2 Vents, Stack Size
Drainage stacks shall be sized in accordance with Table 917.2. Stacks shall be uniformly sized based on the total connected drainage fixture unit ...
910.4 Vents, Waste Stack Size
The waste stack shall be sized based on the total discharge to the stack and the discharge within a branch interval in accordance with Table 910.4 ...
913.4 Vents, Waste Stack Size
The waste stack shall be sized based on the total discharge to the stack and the discharge within a branch interval in accordance with Table 913.4 ...
913.4 Vents, Waste Stack Size
The waste stack shall be sized based on the total discharge to the stack and the discharge within a branch interval in accordance with Table 913.4 ...