901.7.5.2 Sprinkler Systems and Fire Alarm Systems
JUMP TO FULL CODE CHAPTER
Notification that a sprinkler system or fire alarm system, or any part thereof, is or will be out of service shall be made to the department under the following circumstances:
- The sprinkler system or fire alarm system is or will be out of service on more than one floor of a building; or
- With respect to a sprinkler system, the work or repairs cannot be completed, and the system restored to service, within 8 hours of the time the system was placed or went out of service; or
- With respect to a fire alarm system, the work or repairs will require the fire alarm system to be out of service for more than 8 hours in any 24-hour period; or
- One or more other fire protection systems in the area in which a fire protection system is out of service are or will also be out of service at the same time.
Related Code Sections
606.4.2 Duct Systems, Fan Shutdown
or an automatic fire alarm system, provisions shall be made to automatically stop the fans serving the affected area when the sprinkler system or fire alarm system ...
NYC Mechanical Code 2014 > 6 Duct Systems > 606 Smoke Detection Systems Control > 606.4 Controls Operation > 606.4.2 Fan Shutdown
606.4.2 Duct Systems, Fan Shutdown
or an automatic fire alarm system, provisions shall be made to automatically stop the fans serving the affected area when the sprinkler system or fire alarm system ...
NYC Mechanical Code 2008 > 6 Duct Systems > 606 Smoke Detection Systems Control > 606.4 Controls Operation > 606.4.2 Fan Shutdown
903.4.2 Fire Protection Systems, Alarms
Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system ...
NYC Building Code 2014 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.4 Sprinkler System Supervision and Alarms > 903.4.2 Alarms
903.4.2 Fire Protection Systems, Alarms
Department, except in buildings equipped with a fire alarm system. Where a fire alarm system is installed, actuation of the automatic sprinkler system ...
NYC Building Code 2022 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.4 Sprinkler System Supervision and Alarms > 903.4.2 Alarms
903.4.2 Fire Protection Systems, Alarms
on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate ...
NYC Building Code 2008 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.4 Sprinkler System Monitoring and Alarms > 903.4.2 Alarms