903.4 Sprinkler System Supervision and Alarms
JUMP TO FULL CODE CHAPTER
All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures and water-flow switches on all sprinkler systems shall be electrically supervised by the fire alarm system where a fire alarm system is required by Section 907.
Exception:
- Automatic sprinkler systems protecting one- and two-family dwellings.
- Automatic sprinkler systems installed in accordance with NFPA 13R where a common supply main is used to supply both domestic water and the automatic sprinkler systems and a separate shutoff valve for the automatic sprinkler system is not provided.
- Jockey pump control valves that are sealed or locked in the open position.
- Control valves to commercial kitchen hoods, paint spray booths or dip tanks that are sealed or locked in the open position.
- Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position.
- Trim valves to pressure switches in dry, preaction and deluge sprinkler systems that are sealed or locked in the open position.
Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to a central supervising station or when approved by the Fire Department, shall sound an audible signal at a constantly attended location.
Exception:
- Underground key or hub valves in roadway boxes provided by the city or a public utility are not required to be monitored.
- Back flow prevention device test valves, located in limited area sprinkler system supply piping, shall be locked in the open position. In occupancies required to be equipped with a fire alarm system, the back flow preventer valves shall be electrically supervised by a tamper switch installed in accordance with NFPA 72 and separately annunciated.
Approved audible devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building in an approved location or in a location approved by the Fire Department, except in buildings equipped with a fire alarm system. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
Approved supervised indicating control valves shall be provided at the point of connection to the riser on each floor in high-rise buildings.
Related Code Sections
903.4 Fire Protection Systems, Sprinkler System Supervision and Alarms
and water-flow switches on all sprinkler systems shall be electrically supervised by the fire alarm system where a fire alarm system is required by Section ...
NYC Building Code 2014 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.4 Sprinkler System Supervision and Alarms
903.4 Fire Protection Systems, Sprinkler System Monitoring and Alarms
and water-flow switches on all sprinkler systems shall be electrically supervised by the fire alarm system. Exceptions: 1 ...
NYC Building Code 2008 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.4 Sprinkler System Monitoring and Alarms
901.6 Fire Protection Systems, Supervisory Service
Automatic sprinkler systems shall be monitored by an approved supervising ...
901.6 Fire Protection Systems, Supervisory Service
Automatic sprinkler systems shall be monitored by a central supervising station ...
410.6 Special Detailed Requirements Based on Use and Occupancy, Automatic Sprinkler System
located at the voice/alarm communication system required by Section 410.8. The operation of any section of the sprinkler system and the deluge system ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 410 Stages and Platforms > 410.6 Automatic Sprinkler System