1910.107(e)(5) Spraying Containers
JUMP TO FULL CODE CHAPTER
Containers supplying spray nozzles shall be of closed type or provided with metal covers kept closed. Containers not resting on floors shall be on metal supports or suspended by wire cables. Containers supplying spray nozzles by gravity flow shall not exceed 10 gallons capacity. Original shipping containers shall not be subject to air pressure for supplying spray nozzles. Containers under air pressure supplying spray nozzles shall be of limited capacity, not exceeding that necessary for 1 day's operation; shall be designed and approved for such use; shall be provided with a visible pressure gage; and shall be provided with a relief valve set to operate in conformance with the requirements of the Code for Unfired Pressure Vessels, Section VIII of the ASME Boiler and Pressure Vessel Code - 1968, which is incorporated by reference as specified in Sec. 1910.6. Containers under air pressure supplying spray nozzles, air-storage tanks and coolers shall conform to the standards of the Code for Unfired Pressure Vessels, Section VIII of the ASME Boiler and Pressure Vessel Code - 1968 for construction, tests, and maintenance.
Related Code Sections
1910.107(e)(5) Hazardous Materials, Spraying Containers
Containers supplying spray nozzles shall be of closed type or provided with metal covers kept closed. Containers not resting on floors shall ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.107 Spray Finishing Using Flammable and Combustible Materials > 1910.107(e) Flammable Liquids and Liquids With a Flashpoint Greater Than 199.4 °F (93 °C) > 1910.107(e)(5) Spraying Containers
1910.106(a)(1) Hazardous Materials,
Aerosol shall mean a material which is dispensed from its container as a mist, spray, or foam by a propellant under pressure ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.106 Flammable Liquids > 1910.106(a) Definitions > 1910.106(a)(1)
1910.111(f)(3)(iv) Hazardous Materials,
All containers shall be equipped for spray loading (filling in the vapor space) or with an approved vapor return valve of adequate capacity ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.111 Storage and Handling of Anhydrous Ammonia > 1910.111(f) Tank Motor Vehicles for the Transportation of Ammonia > 1910.111(f)(3) Container Appurtenances > 1910.111(f)(3)(iv)
1910.94(c)(1) Occupational Health and Environmental Control, Definitions Applicable to This Paragraph
spraying or metallizing, dipping, flow coating, roller coating, tumbling, centrifuging, or spray washing and degreasing as conducted in self-contained ...
OSHA 1910 General Industry > G Occupational Health and Environmental Control > 1910.94 Ventilation > 1910.94(c) Spray Finishing Operations > 1910.94(c)(1) Definitions Applicable to This Paragraph
1910.94(c)(1)(i) Occupational Health and Environmental Control, Spray-Finishing Operations
spraying or metallizing, dipping, flow coating, roller coating, tumbling, centrifuging, or spray washing and degreasing as conducted in self-contained ...
OSHA 1910 General Industry > G Occupational Health and Environmental Control > 1910.94 Ventilation > 1910.94(c) Spray Finishing Operations > 1910.94(c)(1) Definitions Applicable to This Paragraph > 1910.94(c)(1)(i) Spray-Finishing Operations