R702.7.1 Spray Foam Plastic Insulation for Moisture Control With Class II and III Vapor Retarders
JUMP TO FULL CODE CHAPTER
For purposes of compliance with Tables R702.7(3) and R702.7(4), spray foam with a maximum permeance of 1.5 perms at the installed thickness applied to the interior side of wood structural panels, fiberboard, insulating sheathing or gypsum shall be deemed to meet the continuous insulation moisture control requirement in accordance with one of the following conditions:
- The spray foam R-value is equal to or greater than the specified continuous insulation R-value.
- The combined R-value of the spray foam and continuous insulation is equal to or greater than the specified continuous insulation R-value.
Related Code Sections
R702.7.1 Wall Covering, Spray Foam Plastic Insulation for Moisture Control With Class II and III Vapor Retarders
moisture control requirement in accordance with one of the following conditions: The spray foam R-value is equal to or greater than the specified ...
Residential Code 2021 of Colorado > 7 Wall Covering > R702 Interior Covering > R702.7 Vapor Retarders > R702.7.1 Spray Foam Plastic Insulation for Moisture Control With Class II and III Vapor Retarders
1404.3 Exterior Walls, Vapor Retarders
or freezing of moisture will not damage the materials.
Class I and II vapor retarders with vapor permeance greater than 1 perm when measured by ASTM E96 ...
Building Code 2021 of Colorado > 14 Exterior Walls > 1404 Installation of Wall Coverings > 1404.3 Vapor Retarders
1404.3 Exterior Walls, Vapor Retarders
1404.3.2 is met. Only Class III vapor retarders shall be used on the interior side of frame walls where foam plastic insulating sheathing with a perm ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 14 Exterior Walls > 1404 Installation of Wall Coverings > 1404.3 Vapor Retarders
1405.3 Exterior Walls, Vapor Retarders
1405.3.2 is met. Only Class III vapor retarders shall be used on the interior side of frame walls where foam plastic insulating sheathing with a perm rating ...
Building Code of the Department of Personnel & Administration/Office of the State Architect (DPA/OSA) > 14 Exterior Walls > 1405 Installation of Wall Coverings > 1405.3 Vapor Retarders