722.5.1.3 Spray-Applied Fire-Resistant Materials
JUMP TO FULL CODE CHAPTER
The fire resistance of wide-flange structural steel columns protected with spray-applied fire-resistant materials, as illustrated in Figure 722.5.1(5), shall be permitted to be determined from the following expression:
where:

where:
R | = | Fire resistance (minutes). |
h | = | Thickness of spray-applied fire-resistant material (inches). |
D | = | Heated perimeter of the structural steel column (inches). |
C1 and C2 | = | Material-dependent constants. |
W | = | Weight of structural steel column (pounds per linear foot). |
Exception: The fire resistance of structural steel columns protected with intumescent or mastic fire-resistant coatings shall be determined on the basis of fire-resistance tests in accordance with Section 703.2.
The material-dependent constants, C1 and C2, shall be determined for specific fire-resistant materials on the basis
of standard fire-resistance tests in accordance with Section 703.2. Unless
evidence is submitted to the commissioner substantiating a broader application, this
expression shall be limited to determining the fire resistance of structural steel columns
with weight-to-heated-perimeter ratios (W/D) between the largest and smallest columns for which standard fire-resistance test results are available.
Spray-applied fire-resistant materials shall be identified by density and thickness required for a given fire-resistance rating.
Related Code Sections
722.5.1.3 Fire and Smoke Protection Features, Spray-Applied Fire-Resistant Materials
The fire resistance of wide-flange structural steel columns protected with spray-applied fire-resistant materials, as illustrated in Figure 722.5.1(5 ...
NYC Building Code 2022 > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.5 Steel Assemblies > 722.5.1 Structural Steel Columns > 722.5.1.3 Spray-Applied Fire-Resistant Materials
721.5.1.3 Fire and Smoke Protection Features, Spray-Applied Fire-Resistant Materials
The fire resistance of wide-flange structural steel columns protected with spray-applied fire-resistant materials, as illustrated in Figure 721.5.1(5 ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 721 Calculated Fire Resistance > 721.5 Steel Assemblies > 721.5.1 Structural Steel Columns > 721.5.1.3 Spray-Applied Fire-Resistant Materials
721.5.2.2 Fire-Resistance-Rated Construction, Spray-Applied Fire-Resistant Materials
The provisions in this section apply to unrestrained structural steel beams and girders protected with spray-applied fire-resistant materials. Larger ...
NYC Building Code 2008 > 7 Fire-Resistance-Rated Construction > 721 Calculated Fire Resistance > 721.5 Steel Assemblies > 721.5.2 Structural Steel Beams and Girders > 721.5.2.2 Spray-Applied Fire-Resistant Materials
721.5.1.3.2 Fire and Smoke Protection Features, Identification
Spray-applied fire-resistant materials shall be identified by density and thickness required for a given fire-resistance rating ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 721 Calculated Fire Resistance > 721.5 Steel Assemblies > 721.5.1 Structural Steel Columns > 721.5.1.3 Spray-Applied Fire-Resistant Materials > 721.5.1.3.2 Identification
722.5.1.3.2 Fire and Smoke Protection Features, Identification
Spray-applied fire-resistant materials shall be identified by density and thickness required for a given fire-resistance rating ...
NYC Building Code 2022 > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.5 Steel Assemblies > 722.5.1 Structural Steel Columns > 722.5.1.3 Spray-Applied Fire-Resistant Materials > 722.5.1.3.2 Identification