1910.255(b)(1) Voltage
All external weld initiating control circuits shall operate on low voltage, not over 120 volts, for the safety of the operators.
1910.255(b)(2) Capacitor Welding
Stored energy or capacitor discharge type of resistance welding equipment and control panels involving high voltage (over 550 volts) shall be suitably insulated and protected by complete enclosures, all doors of which shall be provided with suitable interlocks and contacts wired into the control circuit (similar to elevator interlocks). Such interlocks or contacts shall be so designed as to effectively interrupt power and short circuit all capacitors when the door or panel is open. A manually operated switch or suitable positive device shall be installed, in addition to the mechanical interlocks or contacts, as an added safety measure assuring absolute discharge of all capacitors.
1910.255(b)(3) Interlocks
All doors and access panels of all resistance welding machines and control panels shall be kept locked and interlocked to prevent access, by unauthorized persons, to live portions of the equipment.
1910.255(b)(4) Guarding
All press welding machine operations, where there is a possibility of the operator's fingers being under the point of operation, shall be effectively guarded by the use of a device such as an electronic eye safety circuit, two hand controls or protection similar to that prescribed for punch press operation, 1910.217. All chains, gears, operating bus linkage, and belts shall be protected by adequate guards, in accordance with 1910.219 of this part.
1910.255(b)(5) Shields
The hazard of flying sparks shall be, wherever practical, eliminated by installing a shield guard of safety glass or suitable fire-resistant plastic at the point of operation. Additional shields or curtains shall be installed as necessary to protect passing persons from flying sparks. (See 1910.252(b)(2)(i)(C) of this section.)
1910.255(b)(6) Foot Switches
All foot switches shall be guarded to prevent accidental operation of the machine.
1910.255(b)(7) Stop Buttons
Two or more safety emergency stop buttons shall be provided on all special multispot welding machines, including 2-post and 4-post weld presses.
1910.255(b)(8) Safety Pins
On large machines, four safety pins with plugs and receptacles (one in each corner) shall be provided so that when safety pins are removed and inserted in the ram or platen, the press becomes inoperative.
1910.255(b)(9) Grounding
Where technically practical, the secondary of all welding transformers used in multispot, projection and seam welding machines shall be grounded. This may be done by permanently grounding one side of the welding secondary current circuit. Where not technically practical, a center tapped grounding reactor connected across the secondary or the use of a safety disconnect switch in conjunction with the welding control are acceptable alternates. Safety disconnect shall be arranged to open both sides of the line when welding current is not present.

Related Code Sections

1910.255(b) Welding, Cutting, and Brazing, Spot and Seam Welding Machines (Nonportable)
of all resistance welding machines and control panels shall be kept locked and interlocked to prevent access, by unauthorized persons, to live portions ...
1910.255(b)(1) Welding, Cutting, and Brazing, Voltage
All external weld initiating control circuits shall operate on low voltage, not over 120 volts, for the safety of the operators ...
1910.255(b)(4) Welding, Cutting, and Brazing, Guarding
All press welding machine operations, where there is a possibility of the operator's fingers being under the point of operation, shall be effectively ...
1910.255(b)(5) Welding, Cutting, and Brazing, Shields
The hazard of flying sparks shall be, wherever practical, eliminated by installing a shield guard of safety glass or suitable fire-resistant plastic ...
1910.255(b)(9) Welding, Cutting, and Brazing, Grounding
Where technically practical, the secondary of all welding transformers used in multispot, projection and seam welding machines shall be grounded ...