F 107.1 General
Ground coupled and water source heat pumps shall be certified in accordance with AHRI/ASHRAE/ISO 13256-1 for water-to-air heat pumps and AHRI/ASHRAE/ISO 13256-2 for water-to-water heat pumps. DX heat pumps shall be certified in accordance with ASHRAE 194. All heat pump equipment used in DX systems shall comply with AHRI 870. Heat pumps shall be fitted with a means to indicate that the compressor is locked out.
F 107.2 Heat Exchangers
Heat exchangers used for heat transfer or heat recovery shall protect the potable water system from being contaminated by the heat transfer medium. Single-wall heat exchangers shall comply with Section 1218.1. Double-wall heat exchangers shall separate the potable water from the heat transfer medium by providing a space between the two walls that are vented to the atmosphere.
F 107.3 Heat-Transfer Medium
The heat-transfer medium shall be compatible with components with which it comes into contact. Where antifreeze or corrosion inhibitors are used, such solutions shall be approved by the Authority Having Jurisdiction. The heat-transfer fluid flash point shall be not less than 50°F (27.8°C) above the maximum system operating temperature. For DX systems, the heat transfer medium shall be a refrigerant listed in ASHRAE 34 or this code.
F 107.4 Insulation
The temperature of surfaces within reach of building occupants shall not exceed 140°F (60°C) unless they are protected by insulation. Where sleeves are installed, the sleeve insulation shall retain its full size over the length of the material being protected.

Related Code Sections

F 107.0 Geothermal Energy Systems Part I — General, Specific System Components Design
/ISO 13256-2 for water-to-water heat pumps. DX heat pumps shall be certified in accordance with ASHRAE 194. All heat pump equipment used in DX systems ...
1215.0 Hydronics, Hydronic Space Heating
Based on the system design, the heat-distribution units shall be selected in accordance with the manufacturer's specifications ...