// CODE SNIPPET
1102.2 Specific Insulation Requirements
JUMP TO FULL CODE CHAPTER
When Section 1102.1 would require R-38 in the ceiling, R-30 shall be deemed to satisfy the requirement for R-38 wherever the full height of uncompressed R-30 insulation extends over the wall top plate at the eaves. Similarly R-38 shall be deemed to satisfy the requirement for R-49 wherever the full height of uncompressed R-38 insulation extends over the wall top plate at the eaves. This reduction shall not apply to the U -factor alternative approach in Section 1102.1.2 and the Total UA alternative in Section 1102.1.3.
Where Section 1102.1 would require insulation levels above R-30 and the design of the roof/ceiling assembly does not allow sufficient space for the required insulation, the minimum required insulation for such roof/ceiling assemblies shall be R-30. This reduction of insulation from the requirements of Section 1102.1 shall be limited to 500 square feet (46 m2) or twenty per cent of the total insulated ceiling area, whichever is less . This reduction shall not apply to the U-factor alternative approach in Section 1102.1.2 and the Total UA alternative in Section 1102.1.3. .
Access doors from conditioned spaces to unconditioned spaces (e.g., attics and crawl spaces) shall be weatherstripped and insulated to a level equivalent to the insulation on the surrounding surfaces. Access shall be provided to all equipment which prevents damaging or compressing the insulation. A wood framed or equivalent baffle or retainer is required to be provided when loose fill insulation is installed, the purpose of which is to prevent the loose fill insulation from spilling into the living space when the attic access is opened and to provide a permanent means of maintaining the installed R -value of the loose fill insulation.
Steelframe ceilings, walls and floors shall meet the insulation requirements of Table 1102.2.5 or shall meet the U-factor requirements in Table 1102.1.2. The calculation of the U-factor for a steel-frame envelope assembly shall use a series-parallel path calculation method.
Exception: Deleted.
TABLE 1102.2.5
STEEL-FRAME CEILING, WALL AND FLOOR INSULATION (R-VALUE)
WOOD FRAME R-VALUE REQUIREMENT | COLD-FORMED STEEL EQUIVALENT R-VALUEa |
Steel Truss Ceilingsa | |
R-30 | R-38 or R-30 + 3 or R-26 + 5 |
R-38 | R-49 or R-38 + 3 |
R-49 | R-38 + 5 |
Steel Joist Ceilingsb | |
R-30 | R-38 in 2 × 4 or 2 × 6 or 2 × 8 R-49 in any framing |
R-38 | R-49 in 2 × 4 or 2 × 6 or 2 × 8 or 2 × 10 |
Steel Framed Wall | |
R-13 | R-13 + 5 or R15 + 4 or R-21 + 3 or R-0 + 10 |
R-19 | R-13 + 9 or R-19 + 8 or R-25 + 7 |
R-21 | R-13 + 10 or R-19 + 9 or R-25 + 8 |
Steel Joist Floor | |
R-13 | R-19 in 2 × 6 R-19 + R-6 in 2 × 8 or 2 × 10 |
R-19 | R-19 + R-6 in 2 × 6 R-19 + R-12 in 2 × 8 or 2 × 10 |
For SI: 1 inch = 25.4 mm.
- Cavity insulation R-value is listed first, followed by continuous insulation R-value.
- Insulation exceeding the height of the framing shall cover the framing.
Floor insulation shall be installed to maintain permanent contact with the underside of the subfloor decking.
Exterior walls associated with conditioned basements shall be insulated from the top of the basement wall down to 10 feet (3048 mm) below grade or to the basement floor, whichever is less. Walls associated with unconditioned basements shall meet this requirement unless the floor overhead is insulated in accordance with Sections 1102.1 and 1102.2.6.
Slab-on-grade floors with a floor surface less than 12 inches below grade shall be insulated in accordance with Table 1102.1. The insulation shall extend downward from the top of the slab on the outside or inside of the foundation wall. Insulation located below grade shall be extended the distance provided in Table 1102.1 by any combination of vertical insulation, insulation extending under the slab or insulation extending out from the building. Insulation extending away from the building shall be protected by pavement or by a minimum of 10 inches (254 mm) of soil. The top edge of the insulation installed between the exterior wall and the edge of the interior slab shall be permitted to be cut at a 45-degree (0.79 rad) angle away from the exterior wall. Slab-edge insulation is not required in jurisdictions designated by the building official as having a very heavy termite infestation.
As an alternative to insulating floors over crawl spaces, insulation of crawl space walls shall be permitted when the crawl space is not vented to the outside. Crawl space wall insulation shall be permanently fastened to the wall and extend downward from the floor to the finished grade level and then vertically and/or horizontally for at least an additional 24 inches (610 mm). Exposed earth in unvented crawl space foundations shall be covered with a continuous Class I vapor retarder. All joints of the vapor retarder shall overlap by 6 inches (152 mm)and be sealed or taped. The edges of the vapor retarder shall extend at least 6 inches (152 mm) up the stem wall and shall be attached to the stem wall.
Insulation shall not be required on the horizontal portion of the foundation that supports a masonry veneer.
The minimum ceiling insulation R -values shall be R-19 in zones 1 through 4 and R-24 in zones 5 though 8. The minimum wall R -value shall be R-13 in all zones. New wall(s) separating the sunroom from conditioned space shall meet the building thermal envelope requirements.
Related Code Sections
1102.2 Energy Efficiency, Specific Insulation Requirements
of uncompressed R-30 insulation extends over the wall top plate at the eaves. Similarly R-38 shall be deemed to satisfy the requirement for R-49 wherever the full ...
Ohio Residential Code 2013 > 11 Energy Efficiency > 1102 Building Thermal Envelope > 1102.2 Specific Insulation Requirements
1105.2.2 Energy Efficiency, Specific Insulation Requirements
Where Section 1105.2.1 would require insulation levels above R-30 and the design of the roof/ceiling assembly does not allow sufficient ...
Ohio Residential Code 2013 > 11 Energy Efficiency > 1105 Ohio Home Builders Association (OHBA) Alternative Energy Code Option > 1105.2 Building Thermal Envelope > 1105.2.2 Specific Insulation Requirements
1102.2.9 Energy Efficiency, Crawl Space Walls
As an alternative to insulating floors over crawl spaces, insulation of crawl space walls shall be permitted when the crawl space is not vented ...
Ohio Residential Code 2013 > 11 Energy Efficiency > 1102 Building Thermal Envelope > 1102.2 Specific Insulation Requirements > 1102.2.9 Crawl Space Walls
1102.2.1 Energy Efficiency, Ceilings With Attic Spaces
of uncompressed R-30 insulation extends over the wall top plate at the eaves. Similarly R-38 shall be deemed to satisfy the requirement for R-49 wherever the full ...
Ohio Residential Code 2013 > 11 Energy Efficiency > 1102 Building Thermal Envelope > 1102.2 Specific Insulation Requirements > 1102.2.1 Ceilings With Attic Spaces