If the standby system is a generator set inside a building, the system shall be located in a separate room enclosed with 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. System supervision with manual start and transfer features shall be provided at the fire command center.

Related Code Sections

2702.2 Electrical, Where Required
Emergency and standby power systems shall be provided where required by Sections 2702.2.1 through 2702.2.18 ...
3102.8.2 Special Construction, Standby Power
Wherever an auxiliary inflation system is required, an approved standby power-generating system shall be provided. The system shall be equipped ...