In addition to other requirements of this section, HPP gases shall comply with this subsection and the fire code.
1406.3.1 Special Provisions
Where HPP supply gas is carried in pressurized piping, a fail-safe system shall shut off flow due to a rupture in the piping. Where the piping originates from outside the building, the valve shall be located outside the building as close to the bulk source as practical.
1406.3.2 Piping and Tubing Installation
Piping and tubing shall be installed in accordance with approved standards. Supply piping for hazardous production materials having a health hazard ranking of 3 or 4 shall have welded connections throughout, unless an exhausted enclosure is provided.
Exception: Material that is incompatible with ferrous piping shall be permitted to be installed in nonmetallic piping with approved connections.
1406.3.3 Gas-Detection System
Where hazardous production material gas is used or dispensed and the physiological warning properties for the gas are at a higher level than the accepted permissible exposure limit for the gas, a continuous gas-monitoring system shall be provided to detect the presence of a short-term hazard condition. Where dispensing occurs and flammable gases or vapors are capable of being present in quantities in excess of 20 percent of the lower explosive limit, a continuous gas-monitoring system shall be provided. The monitoring system shall be connected to the emergency control station.

Related Code Sections

1406.3 Process Piping, Special Requirements for HPP Gases
In addition to other requirements of this section, HPP gases shall comply with this subsection and the fire code ...
22.11 Special Occupancy Requirements, Compressed Gases and Cryogenic Fluids Code
When sprinkler protection is required, the area in which compressed gases or cryogenic fluids are stored or used shall be protected with a sprinkler ...