// CODE SNIPPET
807.5 Special Inspections for Sound Levels
Go To Full Code Chapter
An approved agency, funded by the building owner, shall furnish report(s) of test findings indicating that the sound level results are in compliance with this section, applicable laws and ordinances, and the construction documents. Discrepancies shall be brought to the attention of the design professional and code official prior to the completion of that work. A final testing report documenting required testing and corrections of any discrepancies noted in prior tests shall be submitted at a point in time agreed upon by the building owner, or building owner's agent, design professional, and the code official for purposes of demonstrating compliance.
807.5.1 Testing for Mechanical and Electrical Generator Equipment Outside of Buildings
Special inspections shall be conducted in accordance with Section 903.1 to demonstrate compliance with the requirements of Section 807.3.1. Testing shall be conducted following the complete installation of the equipment or generators, the installation of sound reduction barriers, and balancing and operation of the equipment or generators. Testing shall be at locations representing the four cardinal directions from the face of the project building. Such testing shall demonstrate that the equipment is capable of compliance with the night-time limits under normal night-time operating conditions, and if higher sound levels are possible during the daytime, compliance with the daytime limits shall also be demonstrated.
807.5.2 Testing for Building System Background Noise
Special inspections shall be conducted in accordance with Section 903.1 to demonstrate compliance with the requirements of Section 807.3.2. Testing shall be executed within not less than 50 percent of the total number of rooms contained in a building or structure of the types listed in Table 807.3.2 for the given occupancy in accordance with Table 903.1. Testing shall occur following the complete installation of the equipment and systems, the installation of any sound reduction barriers, and balancing and operation of the equipment and systems.
807.5.3 Separating Assemblies
Wall and floor-ceiling assemblies that separate a mechanical or emergency generator equipment room or space from the remainder of the building shall have a sound transmission class (STC) of not less than 60 determined in accordance with ASTM E 90 and ASTM E 413, or for concrete masonry and clay masonry assemblies as calculated in accordance with TMS 0302 or as determined in accordance with ASTM E 90 and ASTM E 413.
807.5.4 HVAC Background Sound
HVAC system caused background sound levels for all modes of operation within rooms shall be in accordance with the lower and upper noise criteria (NC) limits as shown in Table 807.3.2. Special inspections shall be required and conducted in accordance with Section 903.1 in order to demonstrate compliance.
Related Code Sections
807.5 Indoor Environmental Quality and Comfort, Special Inspections for Sound Levels
An approved agency, funded by the building owner, shall furnish report(s) of test findings indicating that the sound level results are in compliance ...
807.3 Indoor Environmental Quality and Comfort, Sound Levels
the outdoors or other building space shall achieve sound levels not greater than specified in Sections 807.3.1 and 807.3.2 during the normal operation ...
807.1 Indoor Environmental Quality and Comfort, Sound Transmission and Sound Levels
Where required by Table 302.1, buildings and tenant spaces shall comply with the minimum sound transmission class and maximum sound level ...
Section 807 Indoor Environmental Quality and Comfort, Acoustics
Where required by Table 302.1, buildings and tenant spaces shall comply with the minimum sound transmission class and maximum sound level ...
18.4.6.5 Notification Appliances, Sound Pressure Level
sound pressure level of the audible tone signal shall exceed the masked threshold in one or more octave bands by at least 10 dB in the octave band ...