1704.7.4 Special Inspection of Soils Investigations, Borings and Test Pits
JUMP TO FULL CODE CHAPTER
Boring operations shall be subject to continuous special inspection to verify compliance with Section 1802. Soil sample recovery operations for test pits shall be subject to continuous special inspection to verify compliance with Section 1802.
Exception: Existing boring, test pit and soil investigation records that have been deemed acceptable to the commissioner in accordance with Section 1802.4.2 are not subject to special inspection.
The special inspector's report shall include statements attesting to the following: that borings were performed in accordance with the procedures established in Section 1802.5, that 50 percent or more of the borings were witnessed directly by the registered design professional designated for this special inspection, the identification of those borings, the name and address of the individual(s) that witnessed any other borings, the borings and/or test pits so inspected were made and carried to the depths indicated; that to the best of the special inspector's knowledge and belief, the description and classification of the soils are a true description of the samples recovered from the respective borings and/or test pits: that such samples were recovered at the levels indicated; and that the boring and/or test pit work progressed in such manner that the samples recovered are reasonably representative of the subsurface conditions.
Related Code Sections
1704.7.4 Structural Tests and Special Inspections, Special Inspection of Soils Investigations, Borings and Test Pits
pits shall be subject to continuous special inspection to verify compliance with Section 1802.
Exception: Existing boring, test pit and soil ...
NYC Building Code 2008 > 17 Structural Tests and Special Inspections > 1704 Special Inspections > 1704.7 Soils > 1704.7.4 Special Inspection of Soils Investigations, Borings and Test Pits
1705.6 Special Inspections and Tests, Subsurface Conditions
INSPECTION
PERIODIC SPECIAL INSPECTION
1. Special inspection of subsurface investigations, borings and test pits. Boring and test pit ...
NYC Building Code 2022 > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.6 Subsurface Conditions
1704.7.4 Structural Tests and Special Inspections, Special Inspection of Subsurface Investigations, Borings and Test Pits
Boring and test pit operations shall be subject to continuous special inspection to verify compliance with Section 1802. Soil sample recovery ...
NYC Building Code 2014 > 17 Structural Tests and Special Inspections > 1704 Special Inspections > 1704.7 Subsurface Conditions > 1704.7.4 Special Inspection of Subsurface Investigations, Borings and Test Pits
1803.4 Soils and Foundations, Investigation
The scope of the geotechnical investigation, including the number, types and depths of borings, the number of test pits or the number ...
NYC Building Code 2022 > 18 Soils and Foundations > 1803 Geotechnical Investigations and Material Classifications > 1803.4 Investigation
1802.4 Soils and Foundations, Investigation
The scope of the geotechnical investigation, including the number, types and depths of borings, the number of test pits or the number ...
NYC Building Code 2014 > 18 Soils and Foundations > 1802 Geotechnical Investigations and Material Classifications > 1802.4 Investigation