1704.2.5 Special Inspection of Fabricated Items
JUMP TO FULL CODE CHAPTER
Where fabrication of structural, load-bearing or lateral load-resisting members or assemblies is being conducted on the premises of a fabricator's shop, special inspections of the fabricated items shall be performed during fabrication, except where the fabricator has been approved to perform work without special inspections in accordance with Section 1704.2.5.1.
Special inspections during fabrication are not required where the work is done on the premises of a fabricator approved to perform such work without special inspection. Approval shall be based on review of the fabricator's written fabrication procedures and quality control manuals that provide a basis for control of materials and workmanship, with periodic auditing of fabrication and quality control practices by an approved agency or the building official. At completion of fabrication, the approved fabricator shall submit a certificate of compliance to the owner or the owner's authorized agent for submittal to the building official as specified in Section 1704.5 stating that the work was performed in accordance with the approved construction documents.
Related Code Sections
1704.2.5 Special Inspections and Tests, Special Inspection of Fabricated Items
shop, special inspections of the fabricated items shall be performed during fabrication, except where the fabricator has been approved to perform ...
Building Code 2021 of Illinois > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation > 1704.2 Special Inspections and Tests > 1704.2.5 Special Inspection of Fabricated Items
1704.2.5 Special Inspections and Tests, Special Inspection of Fabricated Items
shop, special inspections of the fabricated items shall be performed during fabrication, except where the fabricator has been approved to perform ...
Building Code 2018 of Illinois > 17 Special Inspections and Tests > 1704 Special Inspections and Tests, Contractor Responsibility and Structural Observation > 1704.2 Special Inspections and Tests > 1704.2.5 Special Inspection of Fabricated Items
1705.10 Special Inspections and Tests, Fabricated Items
Special inspections of fabricated items shall be performed in accordance with Section 1704.2.5 ...
Building Code 2018 of Illinois > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.10 Fabricated Items
1705.11 Special Inspections and Tests, Fabricated Items
Special inspections of fabricated items shall be performed in accordance with Section 1704.2.5 ...
Building Code 2021 of Illinois > 17 Special Inspections and Tests > 1705 Required Special Inspections and Tests > 1705.11 Fabricated Items
1703.6.1 Special Inspections and Tests, Follow-Up Inspection
The owner or the owner's authorized agent shall provide for special inspections of fabricated items in accordance with Section 1704.2.5 ...
Building Code 2021 of Illinois > 17 Special Inspections and Tests > 1703 Approvals > 1703.6 Evaluation and Follow-Up Inspection Services > 1703.6.1 Follow-Up Inspection