5608.4.2 Special Distance Requirements
JUMP TO FULL CODE CHAPTER
The minimum distance requirements of Table 5608.4 shall be adjusted as follows:
- For chain-fused aerial shells and comets and mines to be fired from mortars, racks, or other holders that are sufficiently strong to prevent their being repositioned in the event of an explosive malfunction of the aerial shells, comets, or mines, the minimum required radius shall be the same as that required in Sections 5608.4 and 5608.4.1. For chain-fused aerial shells and comets and mines to be fired from mortars, racks, or other holders that are not sufficiently strong to prevent their being repositioned in the event of an explosive malfunction of the aerial shells, comets, or mines, or if there is doubt concerning the strength of racks holding chain-fused mortars, based upon the largest mortar in the sequence, the minimum required radius shall be double that required in Sections 5608.4 and 5608.4.1.
- Distances from the point of discharge of any firework to a health care or detention and correctional facility, or the bulk storage of materials that have flammability, explosive, or toxic hazard shall be at least twice the distances specified in Table 5608.4.
- The minimum required spectator separation distance for roman candles and cakes that produce aerial shells, comets, or mine effects shall be the same as the minimum required radius specified in Table 5608.4.
- Aerial shells, comets and mines, and roman candles and cakes shall be permitted to be angled if the dud shells or components are carried away from the main spectator area and either of the following requirements is satisfied:
- 4.1. The offset specified in Table 5608.4 is followed.
- 4.2. The separation distance is correspondingly increased in the direction of the angle.
If the offset provided in Table 5608.4 is followed, the mortars or tubes shall be angled so that any dud shells or components fall at a point approximately equal to the offset of the mortars or tubes from the otherwise required discharge point but in the opposite direction.
Related Code Sections
5608.4.2 Explosives and Fireworks, Special Distance Requirements
The minimum distance requirements of Table 5608.4 shall be adjusted as follows:
For chain-fused aerial shells and comets and mines to be fired ...
2015 Virginia Statewide Fire Prevention Code > 56 Explosives and Fireworks > 5608 Fireworks Display > 5608.4 Clearance > 5608.4.2 Special Distance Requirements
5608.4.2 Explosives and Fireworks, Special Distance Requirements
The minimum distance requirements of Table 5608.4 shall be adjusted as follows: For chain-fused aerial shells and comets and mines to be fired from ...
2012 Virginia Statewide Fire Prevention Code > 56 Explosives and Fireworks > 5608 Fireworks Display > 5608.4 Clearance > 5608.4.2 Special Distance Requirements
5608.4.2 Explosives and Fireworks, Special Distance Requirements
The minimum distance requirements of Table 5608.4 shall be adjusted as follows: For chain-fused aerial shells and comets and mines to be fired from ...
2018 Virginia Statewide Fire Prevention Code > 56 Explosives and Fireworks > 5608 Fireworks Display > 5608.4 Clearance > 5608.4.2 Special Distance Requirements
8.5.5.2.2 Installation Requirements,
Sprinklers shall be positioned in accordance with the minimum distances and special requirements of Section 8.6 through Section 8.12 so ...
Standard for the Installation of Sprinkler Systems 2016 of Virginia > 8 Installation Requirements > 8.5 Position, Location, Spacing, and Use of Sprinklers > 8.5.5 Obstructions to Sprinkler Discharge > 8.5.5.2* Obstructions to Sprinkler Discharge Pattern Development > 8.5.5.2.2
8.5.5.2.2 Installation Requirements,
Sprinklers shall be positioned in accordance with the minimum distances and special requirements of Section 8.6 through Section 8.12 so ...
Standard for the Installation of Sprinkler Systems 2013 of Virginia > 8 Installation Requirements > 8.5 Position, Location, Spacing, and Use of Sprinklers > 8.5.5 Obstructions to Sprinkler Discharge > 8.5.5.2* Obstructions to Sprinkler Discharge Pattern Development > 8.5.5.2.2