Waiting areas and similar spaces constructed as required for corridors shall be permitted to be open to a corridor, only where all of the following criteria are met:

  1. The spaces are not occupied for patient sleeping units, treatment rooms, hazardous or incidental use areas as defined in Section 508.2.
  2. The open space is protected by an automatic fire detection system installed in accordance with Section 907.
  3. The corridors onto which the spaces open, in the same smoke compartment, are protected by an automatic fire detection system installed in accordance with Section 907, or the smoke compartment in which the spaces are located is equipped throughout with quick-response sprinklers in accordance with Section 903.3.2.
  4. The space is arranged so as not to obstruct access to the required exits.

Related Code Sections

407.2.1 Special Detailed Requirements Based on Use and Occupancy, Spaces of Unlimited Area
Waiting areas and similar spaces constructed as required for corridors shall be permitted to be open to a corridor, only where all of the following ...
507.8 General Building Heights and Areas; Separation of Occupancies, Group H Occupancies
Group H-2, H-3 and H-4 fire occupancies shall be permitted in unlimited area buildings containing Groups F and S occupancies, in accordance ...
Section 507 General Building Heights and Areas; Separation of Occupancies, Unlimited Area Buildings
and H-4 fire areas shall be permitted in unlimited area buildings having occupancies in Groups F and S, in accordance with the limitations ...