1138A.1.1 Single Wheelchair Passage Width
The minimum clear width for single wheelchair passage shall be 36 inches (914 mm) continuously. (See Figure 11A-1E.)
See Section 1113A for minimum clear width of sidewalks, and Section 1120A for minimum clear width of interior accessible routes.
Exception: 32 inches (813 mm) in width is acceptable at a point not to exceed 24 inches (610 mm) in length. The segments with reduced width shall be separated by segments that are 48 inches (1219 mm) long minimum and 36 inches (914 mm) wide minimum.
1138A.1.2 Width for Two Wheelchairs Passing
The minimum width for two wheelchairs to pass is 60 inches (1524 mm) (See Figure 11A-1E).
An accessible route (exterior and interior) with a clear width less than 60 inches (1524 mm) shall provide passing spaces at intervals of 200 feet (60 960 mm) maximum. Passing spaces shall be either: a space 60 inches (1524 mm) minimum by 60 inches (1524 mm) minimum; or, an intersection of two walking surfaces providing a T-shaped space complying with Section 1138A.1.3.1, where the base and arms of the T-shaped space extend 48 inches (1219 mm) minimum beyond the intersection. (See Figure 11A-1L.)
1138A.1.3 Wheelchair Turning Space
The space required for a wheelchair to make a 180-degree turn shall be a circular clear space of 60 inches (1524 mm) diameter minimum (See Figure 11A-1D(a)); or a T-shaped space complying with Section 1138A.1.3.1. The circular turning space shall be permitted to include knee and toe clearance complying with Section 1138A.2.
If a person in a wheelchair must make a turn around an obstruction, the minimum clear width of the accessible route shall be as required in Section 1138A.1.5.
1138A.1.3.1 T-Shaped Turning Space
A T-shaped turning space shall be within a 60 inch (1524 mm) square minimum with arms and base 36 inches (914 mm) wide minimum. Each arm of the T shall be clear of obstructions 12 inches (305 mm) minimum in each direction, and the base shall be clear of obstructions 24 inches (610 mm) minimum. The space shall be permitted to include knee and toe clearance complying with Section 1138A.2 only at the end of either the base or one arm. (See Figure 11A-1D (b).)
1138A.1.3.2 Surfaces of Turning Spaces
Turning spaces for wheelchairs shall be stable, firm, slip resistant, and shall comply with Section 1110A.3 or Section 1119A.2. Changes in level are not permitted. Slopes not steeper than 1:48 shall be permitted.
1138A.1.4 Clear Floor or Ground Space for Wheelchairs
1138A.1.4.1 Size and Approach
The minimum clear floor or ground space shall be 30 inches by 48 inches (762 mm by 1219 mm). The minimum clear floor or ground space may be positioned for forward or parallel approach to an object (See Figure 11A-1G). Clear floor or ground space may be part of the knee and toe space required under some objects unless otherwise specified.
1138A.1.4.2 Relationship of Maneuvering Clearances to Wheelchair Spaces
One full unobstructed side of the clear floor or ground space for a wheelchair shall adjoin an accessible route or adjoin another wheelchair clear floor space.
If a clear floor space is located in an alcove or otherwise confined on all or a part of three sides, additional maneuvering clearances shall be provided in accordance with the following: (See Figure 11A-1H).
  1. Forward approach. Alcoves shall be 36 inches (914 mm) wide minimum when the depth exceeds 24 inches (610 mm).
  2. Parallel approach. Alcoves shall be 60 inches (1524 mm) wide minimum when the depth exceeds 15 inches (381 mm).
1138A.1.4.3 Surfaces of Wheelchair Spaces
Clear floor or ground spaces for wheelchairs shall be stable, firm, slip resistant, and shall comply with Section 1110A.3 or Section 1119A.2. Changes in level are not permitted. Slopes not steeper than 1:48 shall be permitted.
1138A.1.4.3.1 Gratings
Gratings located in ground and floor surfaces along accessible routes shall be limited to spaces no greater than 1/2-inch (12.7 mm) wide in one direction. If gratings have elongated openings, they shall be placed so that the long dimension is perpendicular to the dominant direction of traffic.
1138A.1.5 Turn Around Obstruction
When the accessible route makes a 180 degree turn around an element which is less than 48 inches (1219 mm) wide, clear width shall be 42 inches (1067 mm) minimum approaching the turn, 48 inches (1219 mm) minimum at the turn and 42 inches (1067 mm) minimum leaving the turn. When the clear width at the turn is 60 inches (1524 mm) minimum, the clear width when approaching and when leaving the turn shall be 36 inches (914 mm) minimum. (See Figure 11A-1C (b).)
When the accessible route makes a 90 degree turn around an element which is more than 48 inches (1219 mm) wide, clear width shall be 36 inches (914 mm) minimum approaching the turn, at the turn and leaving the turn. (See Figure 11A-1C (a).)
Upcodes Diagrams

Related Code Sections

1138A.1 Housing Accessibility, Space Allowances
width less than 60 inches (1524 mm) shall provide passing spaces at intervals of 200 feet (60 960 mm) maximum. Passing spaces shall be either: a space ...
1138A.1 Housing Accessibility, Space Allowances
width less than 60 inches (1524 mm) shall provide passing spaces at intervals of 200 feet (60 960 mm) maximum. Passing spaces shall be either: a space ...
1138A.1 Housing Accessibility, Space Allowances
).      An accessible route (exterior and interior) with a clear width less than 60 inches (1524 mm) shall provide passing spaces at intervals of 200 feet ...
1138A.1.1 Housing Accessibility, Single Wheelchair Passage Width
The minimum clear width for single wheelchair passage shall be 36 inches (914 mm) continuously. (See Figure 11A-1E.) See Section 1113A for minimum ...