// CODE SNIPPET
1324.5.2.2 Sources of Test Gas
2021 Oregon Plumbing Specialty Code > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1324.0 Performance Criteria and Testing Category 1 (Gases, Medical Surgical Vacuum) > 1324.5 Initial Pressure Tests — Medical Gas and Vacuum Systems > 1324.5.2 Initial Cross-Connection Test > 1324.5.2.2 Sources of Test Gas
Go To Full Code Chapter
Sources of test gas shall be disconnected from all piping systems, except for the one system being tested. [NFPA 99:5.1.12.2.4.2]
Upcodes Diagrams
Related Code Sections
1324.5.2.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Sources of Test Gas
Sources of test gas shall be disconnected from all piping systems, except for the one system being tested. [NFPA 99:5.1.12.2.4.2] ...
2021 Oregon Plumbing Specialty Code > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1324.0 Performance Criteria and Testing Category 1 (Gases, Medical Surgical Vacuum) > 1324.5 Initial Pressure Tests — Medical Gas and Vacuum Systems > 1324.5.2 Initial Cross-Connection Test > 1324.5.2.2 Sources of Test Gas
1306.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Certification Tests
Functional testing of pressure relief valves and safety valves.
Functional testing of sources of supply.
Functional testing of alarm systems, including ...
P2503.7 Plumbing Administration, Water-Supply System Testing
). This pressure shall be held for not less than 15 minutes. The water used for tests shall be obtained from a potable water source. Exception: For PEX ...
E 404.5 Manufactured/Mobile Home Parks and Recreational Vehicle Parks, Fuel Gas Piping Test
The manufactured home fuel gas piping system shall be tested only with air before it is connected to the gas supply. The manufactured home gas piping ...
1322.1.5 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Test Coupons
coupons shall also be welded at change of operator, weld head, welding power supply, or gas source. [NFPA 99:5.1.10.5.1.7 — 5.1.10.5.1.9] ...