P2911.2 Sources
Go To Full Code Chapter
On-site nonpotable water reuse systems shall collect waste discharge only from the following sources: bathtubs, showers, lavatories, clothes washers and laundry trays. Water from other approved nonpotable sources including swimming pool backwash operations, air conditioner condensate, rainwater, foundation drain water, fluid cooler discharge water and fire pump test water shall be permitted to be collected for reuse by on-site nonpotable water reuse systems, as approved by the building official and as appropriate for the intended application.
P2911.2.1 Prohibited Sources
Reverse osmosis system reject water, water softener backwash water, kitchen sink wastewater, dishwasher wastewater and wastewater containing urine or fecal matter shall not be collected for reuse within an on-site nonpotable water reuse system.
Upcodes Diagrams
Related Code Sections
1302.2 Nonpotable Water Systems, Sources
On-site nonpotable water reuse systems shall collect waste discharge from only the following sources: bathtubs, showers, lavatories, clothes washers ...
602.3.1 Water Supply and Distribution, Sources
well, dug well, bored well, spring, stream or cistern. Surface bodies of water and land cisterns shall not be sources of individual water supply unless ...
7.9.6.5.3 Compressed Gases, Source
Detection shall be provided at the source cylinder, container, or tank used for delivery of the gas to the point of use ...
7.9.6.5.3 Compressed Gases, Source
Detection shall be provided at the source cylinder, container, or tank used for delivery of the gas to the point of use ...
P2911.2 Water Supply and Distribution, Sources
On-site nonpotable water reuse systems shall collect waste discharge only from the following sources: bathtubs, showers, lavatories, clothes washers ...