1314.6 Source Valves
Go To Full Code Chapter
A shutoff valve shall be placed at the immediate connection of each central supply system to the piped distribution system to allow the entire central supply system, including all accessory devices (e.g., air dryers, final line regulators), to be isolated from the facility. [NFPA 99:5.1.4.2.1]
1314.6.1 Location
The source valve shall be located in the immediate vicinity of the central supply system. [NFPA 99:5.1.4.2.2]
Upcodes Diagrams
Related Code Sections
1314.6 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Source Valves
] The source valve shall be located in the immediate ...
1323.14.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Source Valves
Source valves shall be labeled in substance as follows: SOURCE VALVE FOR THE (SOURCE NAME) [NFPA 99:5.1.11.2.3] ...
1324.5.4.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Source Valve
The source valve shall be closed during this test. [NFPA 99:5.1.12.2.6.2] ...
2021 Oregon Plumbing Specialty Code > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1324.0 Performance Criteria and Testing Category 1 (Gases, Medical Surgical Vacuum) > 1324.5 Initial Pressure Tests — Medical Gas and Vacuum Systems > 1324.5.4 Standing Pressure Tests — For Positive Pressure Medical Gas Piping Systems > 1324.5.4.2 Source Valve
1327.7.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Source Valve
The source valve shall be closed during this test. [NFPA 99:15.4.7.4.6.3] ...
1308.3 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Pressure-Relief Valve Requirements
be located between each final line regulator and the source valve.
They shall have a relief setting that is 50 percent above the normal system ...