// CODE SNIPPET
609.2.4 Solid Fuel Cooking
Go To Full Code Chapter
Solid fuel cooking systems and facilities shall be designed and installed in accordance with the requirements of this section.
609.2.4.1 Cooking Equipment
Cooking equipment burning solid fuel shall be installed on floors of noncombustible construction that extend 3 feet (914 mm) from the cooking equipment in all directions. Cooking equipment burning solid fuel shall not be installed within 3 feet (914 mm) horizontally of combustible surfaces or construction, or within 6 feet (1829 mm) vertically of such surfaces or construction.
Upcodes Diagrams
Related Code Sections
507.2.4 Exhaust Systems, Solid Fuel
Type I hoods for use over solid fuel-burning cooking appliances shall discharge to an exhaust system that is independent of other exhaust systems ...
917.1 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment, Cooking Appliances
Solid fuel-fired ovens shall be tested in accordance with UL 2162 ...
917.5 Specific Appliances, Fireplaces and Solid Fuel-Burning Equipment, Open-Top Broiler Unit Hoods
between the cooking top and combustible material above the hood. The hood shall be at least as wide as the open-top broiler unit and be centered over ...
4.1.2.5 General Requirements,
system that is an integral part of a listed appliance A solid-fuel cooking appliance as addressed in NFPA 96, Standard for Ventilation Control and Fire ...
3.3.3.3.2 Definitions, Solid Fuel-Burning Appliance
A chimney-connected device that burns solid fuel designed for purposes of heating, cooking, or both ...