603.3.7.2 Solar Thermal
Go To Full Code Chapter
Equipment and systems providing heat to fluids or gases through the capture of solar energy shall be capable of being metered so that the peak thermal energy (Btu/h) provided to the building and its systems or to off-site entities can be determined at 15-minute intervals and the amount of heat captured (Btu) for delivery to the building and its systems can be determined intervals of 1 hour or less.
Exception: Systems with a rated output of less than 100 kBtu/hr shall not be required to have the capacity to be metered.