Section 3139B Solar Heating Installations

Go To Full Code Chapter
3139B.1
Solar heating systems shall comply with the following:
  1. Solar heating system suction outlets shall comply with Section 3137B; and
  2. Solar heating system suction outlets shall be located no closer than 5 feet (1525 mm) to any pool inlet fitting; and
  3. The installation of a solar heating system on a new or existing pool shall not interfere with the required turnover rate as specified in Section 3124B nor exceed the pipe flow velocities as specified in Section 3125B.1.