1810.3.9.6 Socketed Drilled Shafts
Go To Full Code Chapter
Socketed drilled shafts shall have a permanent pipe or tube casing that extends down to bedrock and an uncased socket drilled into the bedrock, both filled with concrete. Socketed drilled shafts shall have reinforcement or a structural steel core for the length as indicated by an approved method of analysis.
The depth of the rock socket shall be sufficient to develop the full load-bearing capacity of the element with a minimum safety factor of two, but the depth shall be not less than the outside diameter of the pipe or tube casing. The design of the rock socket is permitted to be predicated on the sum of the allowable load-bearing pressure on the bottom of the socket plus bond along the sides of the socket.
Where a structural steel core is used, the gross cross-sectional area of the core shall not exceed 25 percent of the gross area of the drilled shaft.
Upcodes Diagrams
Related Code Sections
1810.3.9.6 Soils and Foundations, Socketed Drilled Shafts
Socketed drilled shafts shall have a permanent pipe or tube casing that extends down to bedrock and an uncased socket drilled into the bedrock, both ...
1810.3.9.6 Soils and Foundations, Socketed Drilled Shafts
Socketed drilled shafts shall have a permanent pipe or tube casing that extends down to bedrock and an uncased socket drilled into the bedrock, both ...
1808.8.1 Soils and Foundations, Concrete or Grout Strength and Mix Proportioning
4. Socketed drilled shafts
4,000 psi
5. Micropiles
4,000 psi
6. Precast prestressed driven piles
5,000 psi
For ...
1808.8.1 Soils and Foundations, Concrete or Grout Strength and Mix Proportioning
or F 3,000 psi 3. Precast nonprestressed driven piles 4,000 psi 4. Socketed drilled shafts 4,000 psi 5. Micropiles 4,000 psi 6 ...
1810.3.5.3 Soils and Foundations, Steel
for socketed drilled shafts shall have a nominal outside diameter of not less than 18 inches (457 mm), a wall thickness of not less than 3/8 inch (9.5 mm ...