N1103.9 (R403.9) Snow Melt System Controls (Mandatory)
Go To Full Code Chapter
Snow- and ice-melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is greater than 50°F (10°C) and precipitation is not falling, and an automatic or manual control that will allow shutoff when the outdoor temperature is greater than 40°F (4.8°C).
Related Code Sections
N1103.9 [RE] Energy Efficiency, (R403.9) Snow Melt System Controls (Mandatory)
Snow- and ice-melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system ...
R403.9 [RE] Residential Energy Efficiency, Snow Melt and Ice System Controls (Mandatory)
Snow- and ice-melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system ...
C403.12.2 [CE] Commercial Energy Efficiency, Snow- And Ice-Melt System Controls
Snow- and ice-melting systems shall include automatic controls configured to shut off the system when the pavement temperature is above 50°F (10°C ...