106.1.2 Snow Load Posting
Go To Full Code Chapter
[DSA-SS, DSA-SS/CC] When design snow loads at exterior balconies, decks and other elevated walking surfaces exceed 50 psf, the design snow loads shall be posted as for live loads. When design roof (not ground) snow loads exceed 20 psf, the roof design snow loads for each roof level of the building shall similarly be conspicuously posted with signs stating the maximum design roof snow loads.
Related Code Sections
106.1.1 Scope and Administration, Snow Load Posting
[DSA-SS & DSA-SS/CC, OSHPD 1, 2, & 4] Snow loads used in design shall be posted as for live loads ...
106.1.1 Scope and Administration, Snow Load Posting
[OSHPD 1, 1R, 2, 4 & 5] Snow loads used in design shall be posted as for live loads ...
106.1.1 Scope and Administration, Snow Load Posting
[OSHPD 1, 1R, 2, 4 & 5] Snow loads used in design shall be posted as for live loads ...
106.1.2 Scope and Administration, Snow Load Posting
shall be posted as for live loads. When design roof (not ground) snow loads exceed 20 psf, the roof design snow loads for each roof level of the building ...
1617.6 Structural Design, Determination of Snow Loads
the project site is located, and shall be approved by
DSA. See Section 106.1.1 for snow load posting requirements ...