Where required by Section 403.5.4 or 405.7.2, interior exit stairways and ramps shall be smokeproof enclosures or pressurized stairways or ramps in accordance with Section 909.20.
1022.10.1 Termination and Extension
A smokeproof enclosure or pressurized stairway shall terminate at an exit discharge or a public way. The smokeproof enclosure or pressurized stairway shall be permitted to be extended by an exit passageway in accordance with Section 1022.3. The exit passageway shall be without openings other than the fire door assembly required by Section 1022.3.1 and those necessary for egress from the exit passageway. The exit passageway shall be separated from the remainder of the building by 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.

Exceptions:
  1. Openings in the exit passageway serving a smokeproof enclosure are permitted where the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure, and openings are protected as required for access from other floors.
  2. Openings in the exit passageway serving a pressurized stairway are permitted where the exit passageway is protected and pressurized in the same manner as the pressurized stairway.
  3. The fire barrier separating the smokeproof enclosure or pressurized stairway from the exit passageway is not required, provided the exit passageway is protected and pressurized in the same manner as the smokeproof enclosure or pressurized stairway.
  4. A smokeproof enclosure or pressurized stairway shall be permitted to egress through areas on the level of exit discharge or vestibules as permitted by Section 1027.
1022.10.2 Enclosure Access
Access to the stairway within a smokeproof enclosure shall be by way of a vestibule or an open exterior balcony.
Exception: Access is not required by way of a vestibule or exterior balcony for stairways using the pressurization alternative complying with Section 909.20.5.
Upcodes Diagrams

Related Code Sections

1022.10 Means of Egress, Smokeproof Enclosures and Pressurized Stairways and Ramps
Where required by Section 403.5.4 or 405.7.2 of the International Building Code, interior exit stairways and ramps shall be smokeproof enclosures ...
1023.11 Means of Egress, Smokeproof Enclosures
Where required by Section 403.5.4, 405.7.2 or 412.2.2.1, interior exit stairways and ramps shall be smokeproof enclosures in accordance with Section ...
1023.11 Means of Egress, Smokeproof Enclosures
Access to the stairway or ramp within a smokeproof enclosure shall be by way of a vestibule or an open ...
1023.11.2 Means of Egress, Enclosure Access
Access to the stairway or ramp within a smokeproof enclosure shall be by way of a vestibule or an open exterior balcony. Exception: Access ...