Commercial stocks of smokeless propellants shall be stored as follows:
  1. Quantities exceeding 20 pounds (9 kg), but not exceeding 100 pounds (45 kg) shall be stored in portable wooden boxes having walls of not less than 1 inch (25 mm) nominal thickness.
  2. Quantities exceeding 100 pounds (45 kg), but not exceeding 800 pounds (363 kg), shall be stored in nonportable storage cabinets having walls not less than 1 inch (25 mm) nominal thickness. Not more than 400 pounds (182 kg) shall be stored in any one cabinet, and cabinets shall be separated by a distance of not less than 25 feet (7620 mm) or by a fire partition having a fire-resistance rating of not less than 1 hour.
  3. Storage of quantities exceeding 800 pounds (363 kg), but not exceeding 5,000 pounds (2270 kg) in a building shall comply with all of the following:
    1. The warehouse or storage room is not open to unauthorized personnel.
    2. Smokeless propellant shall be stored in nonportable storage cabinets having wood walls not less than 1 inch (25 mm) nominal thickness and having shelves with not more than 3 feet (914 mm) of separation between shelves.
    3. Not more than 400 pounds (182 kg) is stored in any one cabinet.
    4. Cabinets shall be located against walls of the storage room or warehouse with not less than 40 feet (12 192 mm) between cabinets.
    5. The minimum required separation between cabinets shall be 20 feet (6096 mm) provided that barricades twice the height of the cabinets are attached to the wall, midway between each cabinet. The barricades must extend not less than 10 feet (3048 mm) outward, be firmly attached to the wall and be constructed of steel not less than 1/4 inch thick (6.4 mm), 2-inch (51 mm) nominal thickness wood, brick or concrete block.
    6. Smokeless propellant shall be separated from materials classified as combustible liquids, flammable liquids, flammable solids or oxidizing materials by a distance of 25 feet (7620 mm) or by a fire partition having a fire-resistance rating of 1 hour.
    7. The building shall be equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
  4. Smokeless propellants not stored in accordance with Item 1, 2, or 3 shall be stored in a Type 2 or 4 magazine in accordance with Section 5604 and NFPA 495.
Upcodes Diagrams

Related Code Sections

5606.4.2 Explosives and Fireworks, Smokeless Propellants
Smokeless propellants for personal use in quantities not exceeding 20 pounds (9 kg) shall be stored in original containers in occupancies limited ...
5606.4.2 Explosives and Fireworks, Smokeless Propellants
Smokeless propellants for personal use in quantities not exceeding 20 pounds (9 kg) shall be stored in original containers in occupancies limited ...
5606.3 Explosives and Fireworks, Packages
Smokeless propellants shall be stored in approved shipping containers conforming to DOTn 49 CFR Part 173 ...
5606.3.1 Explosives and Fireworks, Repackaging
The bulk repackaging of smokeless propellants, black powder and small arms primers shall not be performed in retail establishments ...
5606.3.1 Explosives and Fireworks, Repackaging
The bulk repackaging of smokeless propellants, black powder and small arms primers shall not be performed in retail establishments ...