708.12.1.3.1 Smoke Vents Located Above the Roof Line
JUMP TO FULL CODE CHAPTER
Where a closed shaft or smoke vent duct penetrates through the roof of the building, the vent shall be located as follows:
- The vent shall be located at least 8 inches (203 mm) above a noncombustible roof assembly or at least 36 inches (914 mm) above a combustible roof assembly.
- The vent shall be located at least 10 feet (3048 mm) from any window, door, exterior stairway, or interior lot line. The vent may be located no less than 5 feet (1524 mm) from any window or door provided that the vent is located at a point higher than the top of such window or door.
- Where the vent is constructed as a window or louver, the sill of the window or louver shall be located at least 36 inches (914 mm)(above the roof assembly).
Related Code Sections
910.5.3.1 Fire Protection Systems, Smoke Vents Located Above the Roof Line
Where a closed shaft or smoke vent duct penetrates through the roof of the building, the vent shall be located as follows: 1. The vent ...
NYC Building Code 2008 > 9 Fire Protection Systems > 910 Smoke and Heat Vents > 910.5 Smoke Venting of Closed Shafts > 910.5.3 Smoke Vent Location > 910.5.3.1 Smoke Vents Located Above the Roof Line
708.12.1.3.1 Fire and Smoke Protection Features, Smoke Vents Located Above the Roof Line
Where a closed shaft or smoke vent duct penetrates through the roof of the building, the vent shall be located as follows: The vent shall ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 708 Shaft Enclosures > 708.12 Enclosure at the Top > 708.12.1 Smoke Venting of Stair and Other Closed Shafts > 708.12.1.3 Smoke Vent Location > 708.12.1.3.1 Smoke Vents Located Above the Roof Line
910.3.3 Fire Protection Systems, Vent Locations
Smoke and heat vents shall be located 20 feet (6096 mm) or more from adjacent lot lines and fire walls and 10 feet (3048 mm) or more from fire ...
NYC Building Code 2008 > 9 Fire Protection Systems > 910 Smoke and Heat Vents > 910.3 Design and Installation > 910.3.3 Vent Locations
Section 910 Fire Protection Systems, Smoke and Heat Vents
). Smoke and heat vents shall be located 20 feet (6096 mm) or more from adjacent lot lines and fire walls and 10 feet (3048 mm ...
910.3.4 Fire Protection Systems, Vent Locations
Smoke and heat vents shall be located 20 feet (6096 mm) or more from adjacent lot lines and fire walls and 10 feet (3048 mm) or more from fire ...
NYC Building Code 2014 > 9 Fire Protection Systems > 910 Smoke and Heat Vents > 910.3 Design and Installation > 910.3.4 Vent Locations