§27-353.2 Smoke Protection for Elevators in E Occupancies
JUMP TO FULL CODE CHAPTER
For an elevator in a high rise building where such elevator serves four or more stories that contain space classified in occupancy Group E (office space), inclusive of any lobby or entry level, such elevator shall meet the following requirements at every level served by such elevator (i) for such buildings erected pursuant to new building applications filed on or after the effective date of this section, or (ii) where two or more new elevator shafts are installed in such buildings in existence on the effective date of this section:
(a) Elevator vestibule required. At every floor above the main entrance floor where the fire command station is located, all elevators shall open into an enclosed elevator vestibule. The elevator vestibule shall be separated from the building occupancy by smoke barriers extending from floor slab to floor slab.
(b) Permitted penetrations. Penetrations in addition to those permitted in section 27-353.3 (smoke barrier) shall be provided with smoke dampers as defined in reference standard RS 13-1, except that a package pass through or communication opening not exceeding one square foot in area need not be provided with smoke dampers.
(c) Access to exits. Access to an exit on any floor through the enclosed elevator vestibule shall be permitted if the occupied areas on that floor have access to at least one other required exit that does not require passing through the elevator vestibule.
(d) On floors with a floor area of less than twenty-five hundred square feet, the commissioner may accept an alternative design or construction method that accomplishes the purposes of this section, or, if the commissioner determines that compliance with this section is impracticable in whole or in part, the commissioner may authorize an exemption from the requirements of this section.
(a) Elevator vestibule required. At every floor above the main entrance floor where the fire command station is located, all elevators shall open into an enclosed elevator vestibule. The elevator vestibule shall be separated from the building occupancy by smoke barriers extending from floor slab to floor slab.
(b) Permitted penetrations. Penetrations in addition to those permitted in section 27-353.3 (smoke barrier) shall be provided with smoke dampers as defined in reference standard RS 13-1, except that a package pass through or communication opening not exceeding one square foot in area need not be provided with smoke dampers.
(c) Access to exits. Access to an exit on any floor through the enclosed elevator vestibule shall be permitted if the occupied areas on that floor have access to at least one other required exit that does not require passing through the elevator vestibule.
(d) On floors with a floor area of less than twenty-five hundred square feet, the commissioner may accept an alternative design or construction method that accomplishes the purposes of this section, or, if the commissioner determines that compliance with this section is impracticable in whole or in part, the commissioner may authorize an exemption from the requirements of this section.
Related Code Sections
§27-353.2 Fire Protection Construction Requirements, Smoke Protection for Elevators in E Occupancies
For an elevator in a high rise building where such elevator serves four or more stories that contain space classified in occupancy Group E (office ...
NYC 1968 Code (Vol I) > 5 Fire Protection Construction Requirements > 5 Prevention of Interior Fire Spread > §27-353 Smoke and Heat Venting > §27-353.2 Smoke Protection for Elevators in E Occupancies
3008.7.1 Elevators and Conveying Systems, Access to Interior Exit Stairway or Ramp
with Section 711. The protected path shall be separated from the enclosed elevator lobby through an opening protected by a smoke and draft control ...
NYC Building Code 2014 > 30 Elevators and Conveying Systems > 3008 Occupant Evacuation Elevators > 3008.7 Occupant Evacuation Elevator Lobby > 3008.7.1 Access to Interior Exit Stairway or Ramp
3008.7.1 Elevators and Conveying Systems, Access to Interior Exit Stairway or Ramp
with Section 711. The protected path shall be separated from the enclosed elevator lobby through an opening protected by a smoke and draft control ...
NYC Building Code 2022 > 30 Elevators and Conveying Systems > 3008 Occupant Evacuation Elevators > 3008.7 Occupant Evacuation Elevator Lobby > 3008.7.1 Access to Interior Exit Stairway or Ramp
708.14 Fire and Smoke Protection Features, Elevator, Dumbwaiter and Other Hoistways
shall be provided in high rise buildings at the following locations: Elevators opening onto a fire-resistance-rated corridor, in all occupancy groups ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 708 Shaft Enclosures > 708.14 Elevator, Dumbwaiter and Other Hoistways
907.2.3 Fire Protection Systems, Group E
A manual and automatic fire alarm system shall be installed in Group E occupancies. When automatic sprinkler systems or smoke detectors are installed ...
NYC Building Code 2014 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required > 907.2.3 Group E