907.8.3 Smoke Detector Sensitivity
JUMP TO FULL CODE CHAPTER
Smoke detector sensitivity shall be checked within one year after installation and every alternate year thereafter. After the second calibration test, where sensitivity tests indicate that the detector has remained within its listed and marked sensitivity range (or 4-percent obscuration light grey smoke, if not marked), the length of time between calibration tests shall be permitted to be extended to not more than 5 years. Where the frequency is extended, records of detector-caused nuisance alarms and subsequent trends of these alarms shall be maintained. In zones or areas where nuisance alarms show any increase over the previous year, calibration tests shall be performed.
Related Code Sections
907.8.3 Fire Protection Systems, Smoke Detector Sensitivity
Smoke detector sensitivity shall be checked within one year after installation and every alternate year thereafter. After the second calibration test ...
Fire Code 2015 of New Jersey > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.8 Inspection, Testing and Maintenance > 907.8.3 Smoke Detector Sensitivity
712.1.3.2 Fire and Smoke Protection Features, Automatic Shutters
immediately upon the actuation of a smoke detector installed in accordance with Section 907.3.1 and shall completely shut off the well opening ...
Building Code 2018 of New Jersey > 7 Fire and Smoke Protection Features > 712 Vertical Openings > 712.1 General > 712.1.3 Escalator Openings > 712.1.3.2 Automatic Shutters
712.1.3.2 Fire and Smoke Protection Features, Automatic Shutters
immediately upon the actuation of a smoke detector installed in accordance with Section 907.3.1 and shall completely shut off the well opening ...
Building Code 2015 of New Jersey > 7 Fire and Smoke Protection Features > 712 Vertical Openings > 712.1 General > 712.1.3 Escalator Openings > 712.1.3.2 Automatic Shutters
907.2.17.1 Fire Protection and Life Safety Systems, Smoke Detectors
Not fewer than one smoke detector listed for the intended purpose shall be installed in all of the following areas: Mechanical equipment ...
Building Code 2018 of New Jersey > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.17 Underground Buildings With Smoke Control Systems > 907.2.17.1 Smoke Detectors
907.2.18.1 Fire Protection Systems, Smoke Detectors
Not fewer than one smoke detector listed for the intended purpose shall be installed in all of the following areas:
Mechanical equipment ...
Building Code 2015 of New Jersey > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.18 Underground Buildings With Smoke Control Systems > 907.2.18.1 Smoke Detectors