The fire fighter's control panel shall provide control capability over the complete smoke control system equipment within the building as follows:
  1. ON-AUTO-OFF control over each individual piece of operating smoke control equipment that can be controlled from other sources within the building. This includes stairway pressurization fans; smoke exhaust fans; supply, return and exhaust fans; elevator shaft fans and other operating equipment used or intended for smoke control purposes.
  2. OPEN-AUTO-CLOSE control over individual dampers relating to smoke control and that are controlled from other sources within the building.
  3. ON-OFF or OPEN-CLOSE control over smoke control and other critical equipment associated with a fire or smoke emergency and that can only be controlled from the fire fighter's control panel.
Exceptions:
  1. Complex systems, where approved, where the controls and indicators are combined to control and indicate all elements of a single smoke zone as a unit.
  2. Complex systems, where approved, where the control is accomplished by computer interface using approved, plain English commands.

Related Code Sections

909.16.2 Fire Protection and Life Safety Systems, Smoke Control Panel
The fire fighter's control panel shall provide control capability over the complete smoke control system equipment within the building as follows ...
909.16.2 Fire Protection and Life Safety Systems, Smoke Control Panel
The fire fighter's control panel shall provide control capability over the complete smoke control system equipment within the building as follows ...
909.16.1 Fire Protection and Life Safety Systems, Smoke Control Systems
Fans within the building shall be shown on the fire fighter's control panel. A clear indication of the direction of airflow and the relationship ...
909.17 Fire Protection and Life Safety Systems, System Response Time
, ducts and other equipment. For purposes of smoke control, the fire fighter's control panel response time shall be the same for automatic or manual smoke ...
909.17 Fire Protection and Life Safety Systems, System Response Time
, ducts and other equipment. For purposes of smoke control, the fire fighter's control panel response time shall be the same for automatic or manual smoke ...