R1001.8 Smoke Chamber
JUMP TO FULL CODE CHAPTER
Smoke chamber walls shall be constructed of solid masonry units, hollow masonry units grouted solid, stone or concrete. The total minimum thickness of front, back and side walls shall be 8 inches (203 mm) of solid masonry. The inside surface shall be parged smooth with refractory mortar conforming to ASTM C199. Where a lining of firebrick not less than 2 inches (51 mm) thick, or a lining of vitrified clay not less than 5/8 inch (16 mm) thick, is provided, the total minimum thickness of front, back and side walls shall be 6 inches (152 mm) of solid masonry, including the lining. Firebrick shall conform to ASTM C1261 and shall be laid with medium-duty refractory mortar conforming to ASTM C199. Vitrified clay linings shall conform to ASTM C315.
The inside height of the smoke chamber from the fireplace throat to the beginning of the flue shall not be greater than the inside width of the fireplace opening. The inside surface of the smoke chamber shall not be inclined more than 45 degrees (0.79 rad) from vertical where prefabricated smoke chamber linings are used or where the smoke chamber walls are rolled or sloped rather than corbeled. Where the inside surface of the smoke chamber is formed by corbeled masonry, the walls shall not be corbeled more than 30 degrees (0.52 rad) from vertical.
Related Code Sections
R1001.8 Chimneys and Fireplaces, Smoke Chamber
Smoke chamber walls shall be constructed of solid masonry units, hollow masonry units grouted solid, stone or concrete. The total minimum thickness ...
Residential Code 2018 of Kansas > 10 Chimneys and Fireplaces > R1001 Masonry Fireplaces > R1001.8 Smoke Chamber
2111.9 Masonry, Smoke Chamber Walls
Smoke chamber walls shall be constructed of solid masonry units, hollow masonry units grouted solid, stone or concrete. The total minimum thickness ...
3.3.266.1 Definitions, Cloud Chamber Smoke Detection
The principle of using an air sample drawn from the protected area into a high-humidity chamber combined with a lowering of chamber pressure ...
National Fire Alarm and Signaling Code 2016 of Kansas > 3 Definitions > 3.3 General Definitions > 3.3.266 Smoke Detection > 3.3.266.1 Cloud Chamber Smoke Detection
2113.12 Masonry, Clay Flue Lining (Installation)
or, in the case of fireplaces, from the top of the smoke chamber to a point above the enclosing walls. The lining shall be carried up vertically ...
Building Code 2018 of Kansas > 21 Masonry > 2113 Masonry Chimneys > 2113.12 Clay Flue Lining (Installation)
Section R1001 Chimneys and Fireplaces, Masonry Fireplaces
Joints in firebrick 1 / 4 " maximum.
Distance from top of opening to throat
F
8"
Smoke chamber wall thickness
Unlined walls
G
6"
8 ...