709.4.2 Smoke-Barrier Walls Enclosing Areas of Refuge or Elevator Lobbies
Go To Full Code Chapter
Smoke-barrier walls used to enclose areas of refuge in accordance with Section 1009.6.4, or to enclose elevator lobbies in accordance with Section 405.4.3, 3007.6.2, or 3008.6.2, shall form an effective membrane enclosure that terminates at a fire barrier wall having a level of fire protection rating not less than 1 hour, another smoke barrier wall or an outside wall. A smoke and draft control door assembly as specified in Section 716.2.2.1.1 shall not be required at each elevator hoistway door opening or at each exit doorway between an area of refuge and the exit enclosure.
Upcodes Diagrams
Related Code Sections
709.4.2 Fire and Smoke Protection Features, Smoke-Barrier Walls Enclosing Areas of Refuge or Elevator Lobbies
Smoke-barrier walls used to enclose areas of refuge in accordance with Section 1009.6.4, or to enclose elevator lobbies in accordance with Section ...
709.4.2 Fire and Smoke Protection Features, Smoke-Barrier Walls Enclosing Areas of Refuge or Elevator Lobbies
Smoke-barrier walls used to enclose areas of refuge in accordance with Section 1009.6.4, or to enclose elevator lobbies in accordance with Section ...
3008.6.2 Elevators and Conveying Systems, Lobby Enclosure
The occupant evacuation elevator lobby shall be enclosed with a smoke barrier having a fire-resistance rating of not less than 1 hour, except ...
3008.6.2 Elevators and Conveying Systems, Lobby Enclosure
The occupant evacuation elevator lobby shall be enclosed with a smoke barrier having a fire-resistance rating of not less than 1 hour, except ...
Section 3006 Elevators and Conveying Systems, Elevator Lobbies and Hoistway Opening Protection
buildings, such lobbies shall comply with Section 405.4.3. Where an area of refuge is required and an enclosed elevator lobby is provided to serve ...